KROHNE IFC 110 Converter User Manual
Page 71
Part C Special applications, functional checks, service, and order numbers Sect. 7.5
05/2003
IFC 110 F
71
Group D
Display
Cause
Remedial action
D 1
LINE INT.
Power failure
Delete error message in
Note: no counting during
RESET/QUIT. menu,
power failure
reset totalizer if necessary.
D 2
OVERFL. I
Current output range
Check instrument parameters
exceeded
and correct if necessary. Error
message is deleted automati-
cally after cause has been
eliminated.
D 3
OVERFL. P
Pulse output range
Check instrument parameters
exceeded
and correct if necessary. Reset
Note:
totalizer. Error message is dele-
totalizer deviation is
ted automatically after cause
possible
has been eliminated.
D 4
ADW
A/D converter range
Error message is deleted
exceeded
automatically after cause
has been eliminated.
D 5
FATAL.ERROR
Fatal Error, all outputs are
Replace signal converter,
set to ”min” values
see Sect. 8.3 or consult KROHNE
Service, having first noted down
hardware information and error
status, see Sect. 7.3, Fct. 2.02.
D 6
TOTALIZER
Counts lost
Delete error message in
(overflow, data error)
RESET/QUIT. menu.
D 7
I SHORT
Short circuit at current
Check electrical connection
output
acc. to Sect. 2.2 and correct if
necessary.
Load
≥ 15 Ω !
D 8
I OPEN
Open current output
Provide load
≤ 500 Ω !
D 9
ADC PARAM.
Fault detected on the
Check measuring accuracy.
D 10
ADC HARDW.
ADC printed circuit
Replace ADC printed circuit
D 11
ADC GAIN
board (see Sect. 8.4) or con-
sult KROHNE Service, having
first noted down hardware
information and error status,
see Sect.. 7.3, Fct. 2.02
D 12
STARTUP,
Hardware fault,
Replace signal converter
cyclic flashing
watchdog trips
(see Sect. 8.3) or consult
KROHNE Service, having first
noted
down
hardware
information and error status,
see Sect. 7.3, Fct. 2.02.
D 13
BUSY
Displays for flow, totalizers
Change setting in Fct. 1.4
and
messages
disabled
D 14
Unsteady display
Low electrical conductivity,
Increase time constant in
high solids content,
Fct. 1.2, refer to Sect. 6.5 and 6.7.
pulsating
flow
D 15
No display
Power supply OFF
Switch on power supply.
Check power supply fuse F5
Replace if blown,
(F6 for DC versions)
in terminal compartment