KROHNE IFC 110 Converter User Manual
Page 59
Part C Special applications, functional checks, service, and order numbers Sect. 6.4
05/2003
IFC 110 F
59
Electrical connection
HART
®
- active
not with multidrop operation
HART
®
- passive
only with multidrop operation
Power supply unit (and section switch amplifier) must be set up accordingly if in use for HART
®
operation. For setting active/passive operation see Sect. 6.8.
Settings and operation
Fct.
Parameter
Point-to-point mode
Multidrop mode
1.05 Function
1 CORRECT. or 2 CORRECT.
OFF
Range I
4-20 mA or I
0%
≥ 4 mA
I
0%
≥ 4 mA
3.09 Communication HART HART
Address
0
01, 02, 03 ..... 15
(use one address at
one time only)
Operation
Current output
active or passive
passive only
For further information on setting the signal converter refer to chapters 4 and 5.
HART
®
operating tools / Device Description (DD)
The signal converter can be operated either via its local operator interface or by means of the
HART
®
communicator, which is available from KROHNE.
Operator control by means of the HART
®
communicator requires a device description (DD) which
we can load for you into the communicator. We can, of course, also load the DDs of all
manufacturers who have filed their DDs with the HART
®
Communication Foundation.
If you wish to use the signal converter in your operating tool, for example, please ask for the
description of the HART
®
command used so that you can address the complete signal converter
functionality via HART
®
.
active
to HART
®
- communicator
or smart-converter
passive
to next
HART
®
- device
power supply unit
to HART
®
- communicator
or Smart- converter
Bürde
≥ 230 Ω