beautypg.com

5 description of functions 5.1 full-scale range q, 2 time constant – KROHNE IFC 110 Converter User Manual

Page 40

background image

Sect. 5.1

Part B IFC 110 F Signal converter

40

IFC 110 F

05/2003

5 Description

of

functions

5.1

Full-scale range Q

100%

Fct. 1.01 FULL SCALE
Press

→ key

Select unit for full-scale range Q

100%

m³/h

(cubic metres per hour)

Liter/Sec

(litres per second)

US.Gal/min

(US gallons per minute)

• User-defined unit, factory setting = ”Liter/h” (litres per hour) or “US MGal/day”,

see Section 5.14

Select with

andkeys.

Use

key to change to numerical setting, 1st number (cursor) flashes.

Set full-scale range Q

100%

The setting range depends on the meter size (DN) and the flow velocity (v):

Q

min

= DN² x v

min

Q

max

= DN² x v

max

(refer to flow table in Section 10.2)

Nom. diameter/meter size
• DN 2.5 – 1200 /

1

/

10

” – 48”:

0.0053

48 860 m³/h

0.0237

218 560 US.Gal/min

• DN 1300 – 3000 / 52” – 120”:

1435

305 360 m³/h

(refer to Section 8.6)

6415

1 366 000 US.Gal/min

Change flashing number (cursor) with

andkeys.

Use

andkeys to shift cursor 1 place to right or left.

Flashing numbers (cursor) can also be directly set with the 10-key keyboard.
Press

key to return to Fct. 1.1 FULL SCALE

Please note that if ”VALUE P” or ”VALUE P2” is displayed after pressing

key:

PULSE/VOL. is set in Fct. 1.06 PULS P and/or in Fct. 1.07 PULS 2 A1, subfunction ”SELECT P”
and/or ”SELECT P2”. Due to the changed full-scale range Q

100%

, the output frequency (F) of the

pulse outputs is either exceeded or not reached:

P

min

= F

min

/ Q

100%

P

max

= F

max

/ Q

100%

Change pulse value accordingly, see Section 5.07 Pulse output P, Fct. 1.06 and/or 2nd pulse
output A1, Fct. 1.07.

5.2 Time

constant

Fct. 1.02 TIMECONST.
Press

key

Select
ALL

(applies to display and all outputs)

ONLY I (applies only to display, current and status outputs)

Select with keys

and ↓.

Press

key to change to numerical setting, 1st number (cursor) flashes.

Set numerical value
0.2 - 99.9 s

(seconds)

Change flashing number (cursor) with keys

and ↓ .

Use

andkeys to shift cursor 1 place to right or left.

Flashing numbers (cursor) can also be directly set with the 10-key keyboard.
Press

key to return to Fct. 1.02 TIMECONST.

π

4

π

4