3 key functions – KROHNE IFC 110 Converter User Manual
Page 30
Sect. 4.3
Part B IFC 110 F Signal converter
30
IFC 110 F
05/2003
4.3 Key
functions
In the following, the cursor or flashing part of the display is shown against a grey background.
To start operator control
Measuring mode
Operator control mode
1 3 . 5 7 1
→
F c t . 1. 0
m 3 / h
O P E R A T I O N
PLEASE NOTE: if ”YES” is selected in Fct. 3.04 ENTRY CODE, ”CodE 1 - - - - - - - - -”
appears in the display after pressing the
→ key.
Enter the password for the entry code which is a sequence of 9 keys:
→ → → ↵ ↵ ↵ ↑ ↑ ↑
(each keystroke confirmed by ” * ”).
To terminate operator control
Press key
↵ any number of times until one of the following menus
Fct. 1.0 OPERATION, Fct. 2.0 TEST or Fct. 3.0 INSTALL is displayed.
Press key
↵
F c t . 3. 0
↵
I N S T A L L.
S T O R E Y E S
Store new parameters: acknowledge by
pressing key
↵. Measuring mode is
continued with new parameters.
New parameters not to be stored:
press key
↑ to display
”STORE NO”.
Measuring mode is continued with the ”old”
parameters after pressing key
↵.
Keyboard with 10 keys
The keyboard with the 10 keys (0-9) is used for setting all flashing numbers (cursor).
Exception:
the digits of the function numbers, such as Fct. 1.03, can only be changed with
keys
↑ or ↓.