beautypg.com

13 flow sensor – KROHNE IFC 110 Converter User Manual

Page 49

background image

Part B IFC 110 F Signal converter Sect. 5.13

05/2003

IFC 110 F

49

5.13 Flow

sensor

Fct. 3.02 FLOW METER
Press

key

DIAMETER = set meter size (see instrument nameplate), presskey

Select size from table of meter sizes:
DN 2.5 – 1200 equivalent to

1

/

10

- 48 inch

DN 1300 – 3000 equivalent to 52 - 120 inch, see Section 8.6.

Select with

and keys.

Press

key to change to subfunction ”FULL SCALE”.

FULL SCALE = set full-scale range, presskey

Set as described in Section 5.1.

Press

key to change to subfunction ”GK VALUE”.

Please note that if ”VALUE P” or ”VALUE P2” is displayed after pressing

key:

PULSE/VOL. is set in Fct. 1.06 PULS P and/or in Fct. 1.07 PULS 2 A1, subfunction ”SELECT P”
and/or ”SELECT P2”. Due to the changed full-scale range Q

100%

, the output frequency (F) of the

pulse outputs is either exceeded or not reached:

P

min

= F

min

/ Q

100%

P

max

= F

max

/ Q

100%

Change pulse value accordingly, see Section 5.08 Pulse output P, Fct. 1.06
and/or 2nd pulse output A1, Fct. 1.07.

GK VALUE = set flow sensor constant GK, presskey

1.0000 - 9.9999 (note information on instrument nameplate, do not change setting)

Change flashing number (cursor) with keys

and ↓ .

Use

andkeys to shift cursor 1 place to right or left.

Flashing numbers (cursor) can also be directly set with the 10-key keyboard.
Press

key to change to subfunction ”FIELD FREQ.”

FIELD FREQ. = set magnetic field frequency, presskey

1/2

1/6

(1/2, 1/6, 1/18 or 1/36 of power frequency, see instrument nameplate,

1/18

1/36 do not change setting, exceptions see Sections 6.4-6.10)

Select with

and keys.

Press

key to change to subfunction ”FLOW DIR.”

(for DC instruments change to subfunction ”LINE FREQ.”).

LINE FREQ. = set power frequency customary in country

where instrument is used, press

key

(Please note: only applies to instruments with DC power unit)
50 Hz

Select with

and keys.

60 Hz

Press

key to change to subfunction ”FLOW DIR.”.

FLOW DIR. = set flow direction, presskey

+ DIR.

(for identification of flow direction see ”+” arrow on flow sensor;

- DIR.

F/R mode: identification of ”positive” flow direction)

Select with

and keys.

Press

key to return to Fct. 3.02 FLOW METER.

Zero check, see Fct. 3.03 and Section 7.1.

Please refer to Section 2.7 ”Factory settings”.