KROHNE IFC 110 Converter User Manual
Page 33
Part B IFC 110 F Signal converter Sect. 4.4
05/2003
IFC 110 F
33
Fct. Text
Description
and
setting
1.04 DISPLAY
Display
functions
→ DISP.FLOW
Selection of flow display
● NO DISP. ● User unit, factory setting ”Liter/h” or ”US MGal/day” (s. Sect. 3.05)
● m³/h
● PERCENT
● Liter/Sec
● BARGRAPH (value and bar graph display in %)
● US.Gal/min
Press
↵ key to change to subfunction ”DISP. TOTAL.”
→ DISP.TOTAL. Selection of totalizer display
● NO DISP. (totalizer is ON but no display)
● OFF (totalizer is OFF)
● + TOTAL.
● - TOTAL.
● +/- TOTAL.
● SUM (
Σ)
● ALL (display single counts or all)
Press
↵ key to change to setting of display unit.
● m³
● Liter
● US.Gal
● User unit, factory setting ”Liter” (s. Sect. 3.05)
Press
→ key to transfer to format setting.
Format
setting
● Auto (exponent notation)
● # . #######
● ##### . ###
● ## . ######
● ###### . ##
● ### . #####
● ####### . #
● #### . ####
● ########
Press
↵ key to change to subfunction ”DISP. MSG.”
→ DISP.MSG.
Additional messages desired during measuring mode?
● NO
● YES (cyclic change with display of measured values)
Press
↵ key to return to Fct. 1.04 DISPLAY.
1.05 CURRENT I
Current output I
→ FUNCT. I
Selecting the current output I function
● OFF (switched off)
● + DIR.
● - DIR. (measurement in one flow direction only)
● 2 DIR. (forward/reverse flow, F/R mode)
Press
↵ key to change to subfunction ”RANGE I”; if ”2 DIR.” is selected
press this key to change to subfunction ”REV. RANGE”.
→ REV.RANGE Setting the full-scale range for reverse flow of Q
100%
(only displayed when ”2 DIR.” is selected)
● 100 PCT. (same as forward flow Q
100%
, see Sect. 1.01)
● PERCENT setting range: 005 - 150 % of Q
100%
(different value for reverse flow)
Press
→ key to change to numerical setting.
Press
↵ key to change to subfunction ”RANGE I”
→ RANGE I
Selecting the measuring range
● 0 - 20 mA
● 4 - 20 mA (fixed ranges)
● mA (user-defined range)
I
0%
- I
100%
(Value I
0%
< I
100%
!)
0 - 16 mA 4 - 20 mA
Press
→ key to change to numerical setting!
Press
↵ key to change to subfunction ”I ERROR”.
→ I ERROR
Selecting the error value
● 22 mA
● 0.0 to I
0%
mA (variable when I
0%
≥ 1 mA, see above)
Press
→ key to change to numerical setting.
Press
↵ key to return to Fct. 1.05 ”CURRENT OUTPUT I”.
1.06 PULS P
Pulse output P
Description of function of pulse output P on the next page.
1.07 STATUS
A1
Status
output
A1
A1 = terminal
or
connected as status or pulse output (P2)
PULS2 A1
2nd pulse output A1
}
s. Fct. 3.07 HARDWARE, ”Terminal A1”
Description of function of status output A1 or 2nd pulse output A1
on the next page.