beautypg.com

KROHNE IFC 110 Converter User Manual

Page 33

background image

Part B IFC 110 F Signal converter Sect. 4.4

05/2003

IFC 110 F

33

Fct. Text

Description

and

setting

1.04 DISPLAY

Display

functions

DISP.FLOW

Selection of flow display

● NO DISP. ● User unit, factory setting ”Liter/h” or ”US MGal/day” (s. Sect. 3.05)

● m³/h

● PERCENT

● Liter/Sec

● BARGRAPH (value and bar graph display in %)

● US.Gal/min

Press

key to change to subfunction ”DISP. TOTAL.”

DISP.TOTAL. Selection of totalizer display

● NO DISP. (totalizer is ON but no display)

● OFF (totalizer is OFF)

● + TOTAL.

● - TOTAL.

● +/- TOTAL.

● SUM (

Σ)

● ALL (display single counts or all)

Press

key to change to setting of display unit.

● m³

● Liter

● US.Gal

● User unit, factory setting ”Liter” (s. Sect. 3.05)

Press

key to transfer to format setting.

Format

setting

Auto (exponent notation)

● # . #######

● ##### . ###

● ## . ######

● ###### . ##

● ### . #####

● ####### . #

● #### . ####

● ########

Press

key to change to subfunction ”DISP. MSG.”

DISP.MSG.

Additional messages desired during measuring mode?

● NO

● YES (cyclic change with display of measured values)

Press

key to return to Fct. 1.04 DISPLAY.

1.05 CURRENT I

Current output I

FUNCT. I

Selecting the current output I function

● OFF (switched off)

● + DIR.

● - DIR. (measurement in one flow direction only)

● 2 DIR. (forward/reverse flow, F/R mode)

Press

key to change to subfunction ”RANGE I”; if ”2 DIR.” is selected

press this key to change to subfunction ”REV. RANGE”.

REV.RANGE Setting the full-scale range for reverse flow of Q

100%

(only displayed when ”2 DIR.” is selected)

● 100 PCT. (same as forward flow Q

100%

, see Sect. 1.01)

● PERCENT setting range: 005 - 150 % of Q

100%

(different value for reverse flow)

Press

key to change to numerical setting.

Press

key to change to subfunction ”RANGE I”

RANGE I

Selecting the measuring range

● 0 - 20 mA

● 4 - 20 mA (fixed ranges)

● mA (user-defined range)

I

0%

- I

100%

(Value I

0%

< I

100%

!)

0 - 16 mA 4 - 20 mA

Press

key to change to numerical setting!

Press

key to change to subfunction ”I ERROR”.

I ERROR

Selecting the error value

● 22 mA

● 0.0 to I

0%

mA (variable when I

0%

≥ 1 mA, see above)

Press

key to change to numerical setting.

Press

key to return to Fct. 1.05 ”CURRENT OUTPUT I”.

1.06 PULS P

Pulse output P

Description of function of pulse output P on the next page.

1.07 STATUS

A1

Status

output

A1

A1 = terminal

or

connected as status or pulse output (P2)

PULS2 A1

2nd pulse output A1

}

s. Fct. 3.07 HARDWARE, ”Terminal A1”

Description of function of status output A1 or 2nd pulse output A1
on the next page.