Sect. 5.7

Part B IFC 110 F Signal converter

44

IFC 110 F

05/2003


I ERROR = set the error value, press key

22 mA

(fixed value)

0.0 - I

0%

mA (variable value, only variable when I

0%

≥ 1 mA, see ”RANGE I” above)

Select with

and keys.

Change flashing number (cursor) with keys

and ↓ . Useandkeys to shift cursor

1 place to right or left.
Flashing numbers (cursor) can also be directly set with the 10-key keyboard.
Press

key to return to Fct. 1.05 CUR. OUTP. I

Please refer to Section 2.7 ”Factory settings”

Refer to Section 2.6 for connection diagrams and to Section 5.16 for characteristics.

5.8

Pulse outputs P and A1


Pulse output P

2nd pulse output A1

for ...

electronic totalizer

electromagnetic or

electronic

totalizers

Terminals

P and P

A1 and A

F

max

at full-scale range Q

100%

10,000 pulses/s

50 pulses/s

F

min

at full-scale range Q

100%

10 pulses/h

10 pulses/h

Max. switching current

30 mA / AC or DC

100 mA / AC or DC

200 mA / DC polarized

(see Section 6.3)

Remark

”PULSOUTP.” must be selected

in Fct. 3.07 HARDWARE,

subfunction ”Terminal A1”


PLEASE NOTE: check that output terminal ”A1” is defined as pulse output in
Fct. 3.07 “HARDWARE”, see Sections 2.2 and 5.17.

Fct. 1.06 PULS P

Fct. 1.07 PULS2 A1

Press

key

and / or

Press

key


FUNCT. P = select function for pulse output, press key

OFF

(switched off, no function)

+ DIR.

(measurement in one direction, refer to selection of main flow direction in

– DIR.

Fct. 3.02 FLOW METER, subfunction ”FLOW DIR.”)

2 DIR.

}

(2 flow directions, F/R mode, forward/reverse)


Select with

and keys.

Press

key to change to subfunction ”SELECT P”.

Exception: when ”OFF” is selected, return to Fct. 1.06 PULS P or Fct. 1.07 PULS2 A1.

SELECT P = select pulse type, presskey

PULSE/VOL.

(pulses per unit volume, flow)

PULSE/TIME

(pulses per unit time for 100 % flow)


Select with

and keys.

Press

key to change to subfunction ”PULSWIDTH”.