beautypg.com

KROHNE IFC 110 Converter User Manual

Page 6

background image

Sect. 1.1

Part A System installation and start-up

6

IFC 110 F

05/2003

1

Electrical connection: power supply

1.1

Location and important installation notes ……………………. PLEASE NOTE !


Electrical connection in accordance with VDE 0100 ”Regulations for the erection of power

installations with nominal voltages up to 1000 V” or equivalent national regulations.


• Do not cross or loop cables inside the terminal compartment.


• Use separate wiring (PG screwed cable entries) for power supply, field current lines, signal

lines, outputs and inputs.


Hazardous areas are subject to special regulations, see Section 6.1 and special installation

instructions for hazardous-duty versions.


• Do not expose signal converter and switchgear cabinets with built-in converters to direct

sunlight. Install a sunshade if necessary.


Signal converters installed in switchgear cabinets require adequate cooling (e.g. by fans

or heat exchangers).


• Do not expose signal converters to intense vibration.


• Keep the distance between the flow sensor and signal converter as small as possible, for

empty pipe detection (EPD)

≤ 20 m / ≤ 66 ft. Observe maximum lengths of signal and field

current lines (see Section 1.3.4).


• Use KROHNE signal line A (type DS, standard) or signal line B (type BTS, bootstrap,

optional), standard length 10 m (33 ft).


• Generally use bootstrap signal lines B (type BTS) for PROFIFLUX 5000 F and VARIFLUX

6000 F flow sensors sized at DN 2.5-15 and 1/10’’-1/2’’ and for contaminated liquids which
tend to form electrically insulating deposits.


• Always calibrate flow sensor and signal converter together. During installation particular care

should therefore be given to identical settings of flow sensor constant GK (see instrument
nameplate of flow sensor). In case GK constants are not identical, the signal converter must
be adjusted to the flow sensor GK (see Sections 4 and 8.5).


Dimensions of signal converter see Section 10.3.










IMPORTANT!
For EEx versions, also pay regard to all directions included in Sect. 6.1 and 13.
Only the EEx flow sensor may be installed in the hazardous area. The EEx
certified signal converter must be installed outside the hazardous area!