Sect. 5.9

Part B IFC 110 F Signal converter

46

IFC 110 F

05/2003

5.9

Status outputs A1 / A2 and D1 / D2

PLEASE NOTE:
Connection diagrams see Section 2.6.

Status outputs

A1

A2

D1

D2

Select Fct _ . _ _

1.07

1.08 1.09 1.10

then press

→ key

Terminals

A1 / A

A2 / A

D1 / D

D2 / D

Max. switching
current

• 100 mA/AC

or DC

100 mA/AC

100 mA/AC

100 mA/AC

• 200 mA/DC

polarized
see Section 6.3

Remark

”STATUSOUTP.”
must be selected
in Fct. 3.07
HARDWARE,
subfunction
”TERMINALS”.

– – –

PLEASE NOTE:
Select function for status outputs,
press

key

ALL ERROR

(indicate all errors)

FATAL.ERROR

(only indicate fatal errors)

OFF

(switched off, no function)

ON

(signals the operation of the flowmeter)

SIGN I

dynamic behaviour

SIGN P/P2

}

F/R mode

of outputs see Fct. 1.02, Sect. 5.2 ”Time constant”

OVERFL. I

exceeding

I = ONLY I

OVERFL. P/P2

}

output ranges

}

P/P2 = ALL

INVERS. A1

(switches output A2 inverse to A1. A1 and A2 then operate as
change-over elements with common centre grounding contact A

⊥. Only

available when status output is selected in Fct. 3.07 ”TERM. A1”.)

INVERS. D1

(switches output D2 inverse to D1. D1 and D2 then operate as
change-over elements with common centre grounding contact D

⊥).

EMPTY PIPE

(signals that measuring tube is empty, only with option ”empty tube
detection”)

AUTO. RNG.

(automatic range change) Setting range 5 - 80 PERCENT

(= high to low range ratio, 1:20 to 1:1.25, value must be higher than that of

Fct. 1.03 L.F. CUTOFF), see Section 5.20.

FULL SCALE, see Section 5.19.

Select flow direction (characteristic) for full-scale range
• + DIR.

• – DIR.

• 2 DIR.

Select with

andkeys.

Define full-scale range
XXX – YYY

normally open contact:

XXX > YYY

0 – 150% 0 – 150%

normally closed contact: XXX < YYY

hysteresis:

difference between XXX and YYY.

Press

key to change to numerical setting, 1st number (cursor) flashes.

Change flashing number (cursor) with keys

and ↓ . Useandkeys to shift cursor

1 place to right or left.
Flashing numbers (cursor) can also be directly set with the 10-key keyboard.
Press

key to return to Fct. 1.07, 1.08, 1.09 or 1.10 for status outputs A1, A2, D1 or D2.