KROHNE IFC 110 Converter User Manual
Page 46
Sect. 5.9
Part B IFC 110 F Signal converter
46
IFC 110 F
05/2003
5.9
Status outputs A1 / A2 and D1 / D2
PLEASE NOTE:
Connection diagrams see Section 2.6.
Status outputs
A1
A2
D1
D2
Select Fct _ . _ _
1.07
1.08 1.09 1.10
then press
→ key
Terminals
A1 / A
⊥
A2 / A
⊥
D1 / D
⊥
D2 / D
⊥
Max. switching
current
• 100 mA/AC
or DC
100 mA/AC
100 mA/AC
100 mA/AC
• 200 mA/DC
polarized
see Section 6.3
Remark
”STATUSOUTP.”
must be selected
in Fct. 3.07
HARDWARE,
subfunction
”TERMINALS”.
– – –
PLEASE NOTE:
Select function for status outputs, press
→ key
• ALL ERROR
(indicate all errors)
• FATAL.ERROR
(only indicate fatal errors)
• OFF
(switched off, no function)
• ON
(signals the operation of the flowmeter)
• SIGN I
dynamic behaviour
• SIGN P/P2
}
F/R mode
of outputs see Fct. 1.02, Sect. 5.2 ”Time constant”
• OVERFL. I
exceeding
I = ONLY I
• OVERFL. P/P2
}
output ranges
}
P/P2 = ALL
• INVERS. A1
(switches output A2 inverse to A1. A1 and A2 then operate as
change-over elements with common centre grounding contact A
⊥. Only
available when status output is selected in Fct. 3.07 ”TERM. A1”.)
• INVERS. D1
(switches output D2 inverse to D1. D1 and D2 then operate as
change-over elements with common centre grounding contact D
⊥).
• EMPTY PIPE
(signals that measuring tube is empty, only with option ”empty tube
detection”)
• AUTO. RNG.
(automatic range change) Setting range 5 - 80 PERCENT
(= high to low range ratio, 1:20 to 1:1.25, value must be higher than that of
Fct. 1.03 L.F. CUTOFF), see Section 5.20.
• FULL SCALE, see Section 5.19.
Select flow direction (characteristic) for full-scale range
• + DIR.
• – DIR.
• 2 DIR.
Select with
↑ and ↓ keys.
Define full-scale range
XXX – YYY
normally open contact:
XXX > YYY
0 – 150% 0 – 150%
normally closed contact: XXX < YYY
hysteresis:
difference between XXX and YYY.
Press
↵ key to change to numerical setting, 1st number (cursor) flashes.
Change flashing number (cursor) with keys
↑ and ↓ . Use → and ← keys to shift cursor
1 place to right or left.
Flashing numbers (cursor) can also be directly set with the 10-key keyboard.
Press
↵ key to return to Fct. 1.07, 1.08, 1.09 or 1.10 for status outputs A1, A2, D1 or D2.