KROHNE IFC 110 Converter User Manual
Page 36
Sect. 4.4
Part B IFC 110 F Signal converter
36
IFC 110 F
05/2003
Fct. Text
Description
and
setting
3.0
INSTALL.
Installation menu
3.01
LANGUAGE
Select language for display texts
● GB / USA (English)
● S (Swedish)
● D (German)
● other languages on request
● F (French)
Press
↵ key to return to Fct. 3.01 “LANGUAGE”.
3.02
FLOWMETER
Set data for flow sensor
→ DIAMETER
Select size from meter size table
● DN 2.5 - 1200 mm equivalent to 1/10 - 48 inch
● DN 1300 - 3000 mm equivalent to 52 - 120 inch (see Sect. 8.6)
Select with
↑ key.
Press
↵ key to change to subfunction “FULL SCALE”.
→ FULL SCALE Full-scale range for flow Q
100%
To set, refer to Fct. 1.01 “FULL SCALE”.
Press
↵ key to change to subfunction “GK VALUE”.
→ VALUE P
Pulse value for pulse output P (Fct. 1.06 ”VALUE P”) and/or
and/or
for the 2nd pulse output A1 (Fct. 1.07 ”VALUE P2”) has been changed.
→ VALUE P
With the ”old” pulse values the output frequency (F) would have been exceeded
or would not have been reached.
P
min
= F
min
/ Q
100%
P
max
= F
max
/ Q
100%
Check new value.
→ GK VALUE
Set primary constant GK
See instrument nameplate of flow sensor.
Range:
● 1.0000 - 15.000
Press
↵
key to change to subfunction “FIELD. FREQ.”.
→ FIELD FREQ. Magnetic field frequency
Values: 1/2, 1/6, 1/18 and 1/36 of power frequency, see instr. nameplate.
Press
↵ key to change to subfunction “FLOW DIR.”;
on DC instruments change to subfunction “LINE FREQ.”.
→ LINE FREQ.
Power frequency customary in the country where the instrument is used
Please
note: this function is limited to instruments with DC supply unit (24 V DC)
to suppress line frequency interferences.
Values:
50 Hz and 60 Hz
Press
↵ key change to subfunction “FLOW DIR.”.
→ FLOW DIR.
Define flow direction (in F/R mode: forward flow).
Set according to direction of arrow on flow sensor:
● + DIR.
● – DIR. Select using
↑ key.
Press
↵ key to return to Fct. 3.02 “FLOWMETER”.
3.03
ZERO SET
Zero calibration
Note: carry out only at ”0” flow and with completely filled measuring tube!
Precautionary
query
● CALIB. NO
Press
↵ key to return to Fct. 3.3 “ZERO SET”.
● CALIB. YES
Press
↵ key to start calibration.
Duration approx. 15-90 s (depending on magnetic field
frequency), current flow rate displayed in the selected unit
(s. Fct. 1.04 ”DISP. FLOW”).
A ”WARNING” sign appears when flow rate ”>0”;
acknowledge by pressing
↵ key.
● STORE NO
(do not store new zero value)
● STORE YES
(store new zero value)
Press
↵ key to return to Fct. 3.03 “ZERO SET”.
3.04
ENTRY CODE
Entry code required to enter setting mode?
● NO
(= entry with
→ only)
● YES (= entry with → and Code 1: → → → ↵ ↵ ↵ ↑ ↑ ↑ )
Press
↵ to return to Fct. 3.04 “ENTRY CODE”.