KROHNE CORIMASS G-MFM 4085 EN User Manual
Page 35
35
Fct. No.
Text
Description and settings
3.3.0
CUR.OUTP. I
Submenu Current output I
For systems with 2 or more current outputs see Sect. 4.7
3.3.1
FUNCTION I
Function current output I
* OFF (O/P current = 0 mA)
* MASS FLOW (Mass flow in range MIN [Fct. 3.3.3] to
MAX [Fct. 3.3.4] output as current in range [Fct 3.3.2]
0/4-20mA)
* DENSITY (Density in range MIN [Fct. 3.3.3] to MAX
[Fct. 3.3.4] output as current in range [Fct 3.3.2]
0/4-20 mA)
* TEMPERATUR (Temperature in range MIN [Fct. 3.3.3]
to MAX [Fct. 3.3.4] output as current in range
[Fct 3.3.2] 0/4-20 mA)
* VOL.FLOW (Volume flow in range MIN [Fct. 3.3.3]
to MAX [Fct. 3.3.4] output as current in range
[Fct 3.3.2] 0/4-20 mA)
SOLUTE.FLOW
Concentration measurement
CONC. BY MASS
functions available if installed
CONC.BY
(see sep. instruction manual).
* DIRECTION (Negative flow gives current of 0/4 mA,
positive flow gives current of 20 mA)
3.3.2
RANGE I
Range for current output I: Select from the following
by pressing
↑
key and then
↵
key
* 0-20 mA
* 4-20 mA
* 0-20/22 mA (O/P = 22 mA when error detected)
* 2/4-20 mA (O/P = 2 mA when error detected)
* 3.5/4-20 mA (O/P = 3.5 mA when error detected)
3.3.3
MIN.VALUE
Value of measured quantity as set by Fct. 3.3.1
or
MIN. FLOW,
that corresponds to the minimum output current
or
MIN. DENSITY
(0 or 4 mA as set by 3.3.2)
or
MIN. TEMP.
or
MIN V.FLOW
or
MIN.CONC.
Menu not available if Function 3.3.1 is set to OFF or
DIRECTION
3.3.4
MAX.VALUE
Value of measured quantity as set by Fct. 3.3.1
or
MAX. FLOW,
that corresponds to an output current of 20 mA
or
MAX. DENSITY,
or
MAX TEMP
or
MAX V.FLOW
or
MAX.CONC
Menu not available if Function 3.3.1 is set to OFF or
DIRECTION