beautypg.com

KROHNE CORIMASS G-MFM 4085 EN User Manual

Page 18

background image

18


2.2

Connection to power

Note information given on the instrument data plate (voltage, frequency)!

Electrical connection in conformity with IEC 364 or equivalent national standard.
Special regulations apply to installation in hazardous areas. Please refer to separate "Ex"
installation instructions.

– The PE protective ground conductor must be connected to the separate U-clamp

terminal in the terminal box of the signal converter.

Do not cross or loop the cables in the terminal box of the signal converter. Use separate
(PG or NPT) cable glands for power and output cables.

Ensure that the screw thread of the round cover on the terminal box is well greased at all
times.

NOTE: The grease used must be non-corrosive to aluminium; typically it must be resin- and

acid-free.

– Protect sealing ring from damage.

Outputs and
connections
see Sect. 2.3

Power and signal connections for MFC 085 K

2.3

Inputs and outputs

The table below shows the input/output connection for the converter. The exact configuration
depends on which optional output modules were fitted in the factory.

Table of input/output connections

Trm.

No.

Option 1

(Current, pulse, status

output and control input )

Option 2

*

(2 current,NGI

status output)

5

Common (-)

Common (-)

6

Current output (+)

Current output 1 (+)

4

Control input

Control input.

4.1

Pulse output

Current output 2 (+)

4.2

Status output (active)

Status output (passive)

*

The inputs/outputs share a common signal ground that is galvanically isolated from ground
(PE).

Please ensure that the information about power given on the
data plate corresponds to the locally available mains voltage.

PE

5

6

4

4.1

4.2

11

12

N L AC

+ DC