• Parameter p5 can be specified on models
with the calibration correction (/CC1 option).
Use the UQ and VL commands to set the
correction values.
UT
Selects the time printout format.
Syntax
UT p1,p2,p3,p4
p1 Time printout format of the alarm printout
The available selections are the same as
those of p2. None is not available.
p2 Time printout format of the message printout
HH:MM Hour:Minute
HH:MM:SS Hour:Minute:Second
M/D H:M Month Day Hour:Minute
M/D H:M:S Month Day Hour:Minute:
Second
YMD H:M:S Month Day Year Hour:Minute:
Second
None
No time printout
p3 Time printout format of the record start time
printout
The available selections are the same as
those of p2. None is not available.
p4 Time printout format of the new chart speed
printout
The available selections are the same as
those of p2. None is not available.
Query
UT?
Example Set the all time printouts to Hour:Minute format.
UTHH:MM,HH:MM,HH:MM,HH:MM
XR
Sets the remote control input
(/R1 option).
Syntax
XR p1,p2
p1 Remote control input terminal number (1 to
5)
p2 Action
NONE
No action
Record On/Off
Start/Stop recording.
Chart speed
Change the chart
speed.
Time adjust
Reset the internal
clock to the nearest
hour.
Math start/stop Start/Stop
computation.
Math reset
Reset computation.
Manual print
Execute manual
print.
Alarm Ack
Execute alarm
acknowledge.
Message1
Print message 1
Message2
Print message 2
Message3
Print message 3
Message4
Print message 4
Message5
Print message 5
Priority R_RCD
Priority to remote
recording
BatchCMT switch
Batch comment
switching
Query
XR[p1]?
Example Assign the printout of message 2 to the remote
control input of terminal number 1.
XR1,Message2
Description • Math start/stop and Math reset can be
specified on models with the computation
function (/M1 option).
• “
Priority R_RCD” and “BatchCMT
switch” can be set on products with header
printout (/BT1 option).
YS
Sets the RS-422A/485 interface
(/C3 option).
Syntax
YS p1,p2,p3,p4,p5
p1 Address (1 to 32)
p2 Baud rate (1200, 2400, 4800, 9600, 19200,
38400)
p3 Data length (7, 8)
p4 Parity check (ODD, EVEN, NONE)
p5 Protocol (NORMAL, MODBUS)
Query
YS?
Example Set the address to 2, the baud rate to 9600, the
data length to 8, the parity check to ODD, and
the NORMAL protocol.
YS2,9600,8,ODD,NORMAL
Description • The settings specified by this command and
saved using the XE command take effect after
the recorder is power cycled.
• If p5 is set to MODBUS, Modbus slave is
selected.
XQ
Sets the TLOG timer
(/M1 option).
When not using the timer
Syntax
XQ p1,p2
p1 Timer number (1 or 2)
p2 Timer type (OFF)
Query
XQ[p1]?
Example Disable the number 1 timer.
XQ1,OFF
When using an absolute timer
Syntax
XQ p1,p2,p3,p4,p5,p6
p1 Timer number (1 or 2)
p2 Timer type (ABSOLUTE)
p3 Interval (10min, 12min, 15min, 20min,
30min, 1h, 2h, 3h, 4h, 6h, 8h, 12h, 24h)
p4 Reference time (fixed to HH format)
HH
Hour (00 to 23)
p5 Reset/not reset the data when the timer
expires (ON/OFF)