App index, Sc sets the chart speed, Sd sets the date and time – Yokogawa µR20000 User Manual
Page 56: Vt sets the dot printing interval (dot model), Sz sets zone recording, Sp sets the partial expanded recording
Commands
1
2
3
4
5
6
App
Index
IM 04P01B01-17E
4-13
SC
Sets the chart speed.
Syntax
SC p1
p1 Chart speed
Query
SC?
Example Set the chart speed to 25 mm/h.
SC25
Description Select the chart speed from the list of choices
below.
Pen model
5 to 12000 mm/h (82 levels, see section 4.3)
Dot model
1 to 1500 mm/h (1 mm steps)
SD
Sets the date and time.
Syntax
SD p1
p1 Date and time (fixed to the YY/MM/DD_HH:
MM:SS format)
YY
Year (00 to 99, the lower 2
digits)
MM
Month (01 to 12)
DD
Day (01 to 31)
_
Space
HH
Hour (00 to 23)
MM
Minute (00 to 59)
SS
Second (00 to 59)
Query
SD?
Example Set the recorder clock to 13:00:00, December 1,
2004.
SD04/12/01 13:00:00
Description • The format of p1 is fixed to 17 characters. An
error results if a space is inserted in positions
other than the specified positions.
• On the µR10000 with system version 1.02 or
earlier, the parameter p2 can be used.
p2 Standard time or DST (winter, summer)
Winter Standard time
Summer DST
VT
Sets the dot printing interval
(dot model).
Syntax
VT p1
p1 Dot printing interval setting.
AUTO
Automatically adjust the dot
printing interval according to
the chart speed.
FIX
Record at the fastest printing
interval.
Query
VT?
Example Record at the fastest printing interval.
VTFIX
Description When trend recording is performed on 6
channels, the fastest printing interval is 10
seconds.
SZ
Sets zone recording.
Syntax
SZ p1,p2,p3
p1 Channel number
p2 Leftmost position of the zone (µR10000: 0 to
95, µR20000: 0 to 175) [mm]
p3 Rightmost position of the zone (µR10000: 5
to 100, µR20000: 0 to 180) [mm]
Query
SZ[p1]?
Example Display channel 02 in a zone between 30 and 50
mm.
SZ02,30,50
Description • Be sure that p3 is greater than p2 and that the
zone width (p3 – p2) is greater than or equal
to 5 mm.
• On models with the computation function
(/M1 option), computation channels can be
specified.
SP
Sets the partial expanded
recording.
Syntax
SP p1,p2,p3,p4
p1 Channel number
p2 Partial expanded recording ON/OFF (ON,
OFF)
p3 Boundary position (1 to 99) [%]
p4 Boundary value
Query
SP[p1]?
Example Set the 25% position of channel 01 to 1.000 V.
SP01,ON,25,1000
Description • When the input range is set to SKIP (SR
command), p2 cannot be turned ON.
• Set p3 as a percentage where 100 mm is
assumed to be 100%.
• Parameter p4 can be set in the range (leftmost
value of span + 1) to (rightmost value of span
– 1). If scaling is enabled, the range is (leftmost
value of scaling – 1) to (rightmost value of
scaling + 1). Set the parameter using an
integer.
• This setting is possible when partial expanded
recording is enabled (UK command).
• This command cannot be used if the partial
expanded recording range does not exist
(when the span width is set to 1, for example).
• On models with the computation function
(/M1 option), computation channels can be
specified.
• When the computation equation setting (SO
command) is turned OFF, p2 cannot be turned
ON.
4.4 Setting Commands