beautypg.com

Yokogawa µR20000 User Manual

Page 40

background image

3-12

IM 04P01B01-17E

Input Register Data

39001

Year (4 digits)

39002

Month

39003

Day

39004

Hour

39005

Minute

39006

Second

39007

Millisecond

39008

Summer/Winter time

• The data is a 16- bit signed integer.

Hold register Data

40001

Communication input data of C01

40002

Communication input data of C02

40003

Communication input data of C03

40004

Communication input data of C04

40005

Communication input data of C05

40006

Communication input data of C06

40007

Communication input data of C07

40008

Communication input data of C08

40009

Communication input data of C09

40010

Communication input data of C10

40011

Communication input data of C11

40012

Communication input data of C12

40013

Communication input data of C13

40014

Communication input data of C14

40015

Communication input data of C15

40016

Communication input data of C16

40017

Communication input data of C17

40018

Communication input data of C18

40019

Communication input data of C19

40020

Communication input data of C20

40021

Communication input data of C21

40022

Communication input data of C22

40023

Communication input data of C23

40024

Communication input data of C24

• Registers corresponding to models with the /M1 computation function option.
• Pen model: C01 to C08, dot model: C01 to C12 (µR10000), C01 to C24 (µR20000)
• The data is a 16-bit signed integer.
• When writing to the register: A 16- bit signed integer only can be input.
• When reading from the register: The communication input data, a floating point, is converted

to a 16- bit signed integer and output.

Hold registers Data

40301

Communication input data of C01 (lower word)

40302

Communication input data of C01 (upper word)

40303

Communication input data of C02 (lower word)

40304

Communication input data of C02 (upper word)

40305

Communication input data of C03 (lower word)

40306

Communication input data of C03 (upper word)

40307

Communication input data of C04 (lower word)

40308

Communication input data of C04 (upper word)

40309

Communication input data of C05 (lower word)

40310

Communication input data of C05 (upper word)

40311

Communication input data of C06 (lower word)

40312

Communication input data of C06 (upper word)

40313

Communication input data of C07 (lower word)

40314

Communication input data of C07 (upper word)

40315

Communication input data of C08 (lower word)

40316

Communication input data of C08 (upper word)

40317

Communication input data of C09 (lower word)

3.4 Modbus Slave Protocol Specifications

This manual is related to the following products: