3.4 Modbus Slave Protocol Specifications

The Modbus slave protocol specifications of the recorder are as follows:

Serial Interface

Item

Specifications

Transmission medium

RS-422A/485

Flow control

None only

Baud rate

Select from 1200, 2400, 4800, 9600, 19200, or 38400 [bps]

Start bit

Fixed to 1 bit

Stop bit

Fixed to 1 bit

Parity check

Select odd, even, or none (no parity).

Transmission mode

RTU (Remote Terminal Unit) mode only

• Data length: 8 bits

• Data interval: 24 bits or less*

• Error detection: Uses CRC-16

* Determines message termination with a time interval to 3.5

characters or more.

Maximum number of

connected units

Four-wire system: 32 slave devices
Two-wire system: 31 slave devices

Slave Address

Address that can be set 1 to 32

Supported Functions

The function codes of the Modbus slave protocol that the recorder supports are shown
below. The recorder does not support broadcast commands.

Function Code

Specifications

Operation

3

Read the hold register (4xxxx).

The master device reads the

communication input data

written using function codes 6

and 16.

4

Read the input register (3xxxx).

The master device loads the

computed, measured, alarm,

and time data of the recordr.

6

Single write to hold register (4xxxx) The master device writes to

the communication input data

of the recorder.

8

Loopback test

The master device performs a

loopback test of the recorder.

The recorder only supports

message return (test code

0x00*)

16

Write to the hold register (4xxxx)

The master device writes to

the communication input data

of the recorder.

* Hexadecimal “00”

Communication Input Data

You can use the communication input data by describing it in the computing equations for
the computation channels.