beautypg.com

Functional construction, Setting/measurement server, Modbus slave – Yokogawa µR20000 User Manual

Page 16

background image

1-4

IM 04P01B01-17E

1.2 Communication Functions Using the RS-

422A/485 Communication Interface (/C3

Option)

The recorder can be equipped with an optional RS-422A/485 communication interface.
For details on how to use the RS-422A/485 communication interface, see chapter 3.

Functional Construction

The following figure shows the relationship between the communication function of
the recorder and the RS-422A/485 communication interface. Perform communication
according to the respective protocol.

* Protocol is a set of rules that two computers use to communicate via a communication line (or

network).

PC

Connect the recorder and the

PC using a serial cable.

Setting/Measurement Server

Dedicated protocol

Protocol

Interface

RS-422A/485

Modbus Slave

Modbus protocol

Communication functions of the recorder

Application

Setting/Measurement Server

The functions are the same as those of the Setting/Measurement server of the Ethernet
interface. See page 1-1.

• RS-422A/485 communication interface settings: Section 3.5
• Commands: Section 4.2
• RS-422A/485 dedicated commands: Section 4.8
• Data output format: Chapter 5

Modbus Slave

• The Modbus protocol can be used to read the measured/computed data on your PC

by reading the input registers of the recorder. The communication input data can be
written or read by writing/reading the hold register of the recorder.

• For details on the Modbus function codes that the recorder supports, see section 3.4.
• This function can be used only when communicating via the serial interface (option).
• For a description on the settings required in using this function, see section 3.5.

Data from slave device

Data to slave device

Modbus master device

Modbus slave device

Serial communication

Recorder

This manual is related to the following products: