3.5 Setting the Serial Interface
The serial interface must be configured.
Setup Items
RS422/485
Address
End
Baud rate
Data length
Parity
Protocol
Procedure
For a description of the basic operations, see “Basic Key Operations” on page vi.
Entering Basic Setting Mode
Hold down the
MENU
key for 3 seconds to display the Setting mode screen.
Next, hold down both the
(
DISP
) key and the
(
FUNC
) key for 3 seconds to
display the Basic Setting mode screen.
Note
To cancel an operation, press the
ESC key.
1.
Press the
key to select
RS422/485 and then press the key.
Basic=RS422/485
2.
Press the
key to select the recorder’s address and then press the key.
Address=1
3.
Press the
key to select the
Baud rate value and then press the key.
Baud rate=38400
4
Press the
key to select the
Data length value and then press the key.
Data length=8
5
Press the
key to select the
Parity value and then press the key.
Parity=Even
6.
Press the
key to select the
NORMAL or MODBUS value and then press the
key.
The setting complete screen appears.
Protocol=NORMAL
RS422/485
Setting complete
Saving the Settings
1.
Press the
ESC key to return to the Basic= screen.
2.
Press the
key to select
End and then press the key.
3.
Press the
key to select
Store and then press the key.
The settings are activated, and the Operation mode screen appears.
* When the key or key is pressed while holding down the
SHIFT key, the operation is reversed as
when the respective key is pressed by itself.