Modbus error response, Modbus error response -13, App index – Yokogawa µR20000 User Manual
Page 41
3-13
IM 04P01B01-17E
Using
the
RS-422A/485
Communication
Interface
(/C3
Option)
1
2
3
4
5
6
App
Index
Hold registers Data
40318
Communication input data of C09 (upper word)
40319
Communication input data of C10 (lower word)
40320
Communication input data of C10 (upper word)
40321
Communication input data of C11 (lower word)
40322
Communication input data of C11 (upper word)
40323
Communication input data of C12 (lower word)
40324
Communication input data of C12 (upper word)
40325
Communication input data of C13 (lower word)
40326
Communication input data of C13 (upper word)
40327
Communication input data of C14 (lower word)
40328
Communication input data of C14 (upper word)
40329
Communication input data of C15 (lower word)
40330
Communication input data of C15 (upper word)
40331
Communication input data of C16 (lower word)
40332
Communication input data of C16 (upper word)
40333
Communication input data of C17 (lower word)
40334
Communication input data of C17 (upper word)
40335
Communication input data of C18 (lower word)
40336
Communication input data of C18 (upper word)
40337
Communication input data of C19 (lower word)
40338
Communication input data of C19 (upper word)
40339
Communication input data of C20 (lower word)
40340
Communication input data of C20 (upper word)
40341
Communication input data of C21 (lower word)
40342
Communication input data of C21 (upper word)
40343
Communication input data of C22 (lower word)
40344
Communication input data of C22 (upper word)
40345
Communication input data of C23 (lower word)
40346
Communication input data of C23 (upper word)
40347
Communication input data of C24 (lower word)
40348
Communication input data of C24 (upper word)
• Registers corresponding to models with the /M1 computation function option.
• Pen model: C01 to C08; Dot model: C01 to C12 (µR10000), C01 to C24 (µR20000)
• The data is a floating point.
• When writing to the register: The values that can be input are –9.9999E29 to –1E–30, 0,
and 1E–30 to 9.9999E29.
If a value exceeding this range is input, a computation error will occur when using the value
on computation channels.
Modbus Error Response
The recorder returns the following error codes to the master device. For the error
messages related to communications that the recorder displays, see appendix 4.
Code
Meaning
Cause
1
Bad function code
Unsupported function request.
2
Bad register number
Attempted to read/write to a register that
has no corresponding channel.
3
Bad number of registers
The specified number of registers is less
than or equal to 0 or greater than or equal
to 126 (when reading)/124 (when writing).
However, no response is returned for the following cases.
• CRC error
• Errors other than those in the table above.
3.4 Modbus Slave Specifications