IM MV1000-17E

4.5 Setting Commands

(Control)

BT

Sets a batch name

Syntax

BT p1,p2,p3
p1 1
p2 Batch number (up to 32 alphanumeric

characters)

p3 Lot number (up to 8 digits)

Query

BT[ p1]?

Example Set the batch name configuration to batch

number PRESS5LINE and lot number 007.
BT1,PRESS5LINE,007

BU

Sets a batch comment

Syntax

BU p1,p2,p3
p1 1
p2 Comment number (1 to 3)
p3 Comment character sting (up to 50

characters)

Query

BU[ p1,[ p2]]?

Example Set comment number 2 to “THIS_PRODUCT_IS

_COMPLETED.”
BU1,2,THIS_PRODUCT_IS_COMPLETED

UD

Switches the display

To switch back to the display that was shown

before you started to change the settings with

communication commands

Syntax

UD p1
p1 Screen switch (0)

Example Switch back to the display that was shown

before you started to change the settings with
communication commands.
UD0

To change to one screen display

Syntax

UD p1,p2,p3
p1 Screen switch (1)
p2 Display item

TREND

Trend display

DIGITAL

Digital display

BAR

Bar graph display

OVERVIEW Overview display

(alarm indicator)

ALARM

Alarm summary display

MESSAGE

Message summary display

MEMORY

Memory summary display

MODBUS-M Modbus master status display
MODBUS-C Modbus client status display
RELAY

Relay status display

REPORT

Report display

HISTRICAL Historical display
COLUMN_BAR Stacked bar graph

p3 Group number

Example Set the display to one screen trend display and

set the group number to 4.
UD1,TREND,4

Description • The setting p2=MODBUS-M is valid only if the

serial interface protocol is set to MODBUS-M.

• The setting p2=REPORT or COLUMN_BAR

is valid only on models with the /M1 MATH
option.

To change to 4 panel display

Syntax

UD p1,p2,p3,p4,p5,p6,p7,p8,p9

p1 Screen switch (2)
p2 Screen 1 type (see SY (Sets the four panel

display))

p3 Group number to be displayed on screen 1
p4 Screen 2 type (see SY (Sets the four panel

display))

p5 Group number to be displayed on screen 2
p6 Screen 3 type (see SY (Sets the four panel

display))

p7 Group number to be displayed on screen 3
p8 Screen 4 type (see SY (Sets the four panel

display))

p9 Group number to be displayed on screen 4

Example Assign group 1 to screen 1, group 2 to screen 2,

group 3 to screen 3, group 4 to screen 4, and set
all screen types to trend display.
UD2,TREND,1,TREND,2,TREND,3,TREND,4

Description This setting is valid on the MV2000.

To display the specified 4 panel number

Syntax

UD p1,p2
p1 Display type (3)
p2 4 panel configuration number

0

Display the specified 4 panel
configuration screen.

1–4

Display the 4 panel configuration
specified by SY (sets the four
panel display).

To set the operation screen switching

Syntax

UD p1,p2,p3,p4,p5,p6,p7
p1 Screen switch (4)
p2 Automatic display switching ON/OFF
p3 Switch between all channel display and

group display (ALL, GROUP)

p4 Scale display ON/OFF
p5 Digital display ON/OFF
p6 Message display method

1

Normal display

2

List display

p7 Trend space ON/OFF
p8 Auto zone ON/OFF
p9 Fine grid ON/OFF

4.5 Setting Commands (Control)