Using the Ethernet Interface

1

2

3

4

5

6

7

App

Index

Basic Settings

Specify the SMTP server and POP before SMTP.

• SMTP server name

Enter the host name or IP address of the SMTP server.

• Port number

Unless specified otherwise, set the number to the default value. The default value is

25.

• Security

If you need to use POP before SMTP, set Security to

PbS.

Recipients

Set the recipient e-mail addresses.

• Recipient 1 and Recipient 2

Enter e-mail addresses. You can enter multiple addresses in each recipient box.

Separate each address with a space. You can enter up to 150 characters.

• Sender

Enter the sender e-mail address. You can enter up to 64 characters.

POP3 Settings

If you need to use POP before SMTP, specify the POP3 server.

For the POP3 login procedure, see “Setting the POP3 Server Connection” in this section.

• POP3 Server name

Enter the host name or IP address of the POP3 server.

• Port number

Unless specified otherwise, set the number to the default value. The default value is

110.

• Login name

Enter the POP3 server login name.

• Password

Enter the POP3 server login password. You can enter up to 32 characters.

Alarm Settings

Specify the settings for sending e-mail when alarms occur or clear.

• Recipient 1 and Recipient 2

Specify the recipients. For

Recipient 1 and Recipient 2, select On to send e-mail or

Off to not send e-mail.

• Active Alarms

Sends an e-mail when an alarm occurs or clears. For alarms 1 to 4, select

On to send

e-mail or

Off to not send e-mail.

• Include INST

Select

On to attach instantaneous value data. The data that is attached is the

instantaneous value that is measured at the time the e-mail is transmitted.

• Include source URL

Select

On to attach the source URL. You can attach the URL when the Web server is

enabled.

• Subject

Enter the subject of the e-mail using up to 32 alphanumeric characters. The default

subject is

Alarm_summary.

• Header 1 and Header 2

Enter Header 1 and Header 2 using up to 64 characters.

2.3 Sending E-mail Messages