Tu sets an event action, Sk sets a computation constant – Yokogawa Button Operated MV2000 User Manual
Page 92
4-18
4.4 Setting Commands (Setting)
IM MV1000-17E
If p2 is set to WEEK (day of week/time designation)
Syntax
TK p1,p2,p3,p4,p5
p1 Timer number (1 to 4)
p2 Timer designation (WEEK)
p3 Designation of the day of the week (SUN,
MON, TUE, WED, THU, FRI, SAT)
p4 Time (hh:mm) (00:00 to 23:59)
p5 Timer operation (SINGLE, REPEAT)
If p2 is set to MONTH (day/time designation)
Syntax
TK p1,p2,p3,p4,p5
p1 Timer number (1 to 4)
p2 Timer designation (MONTH)
p3 Day (1 to 28)
p4 Time (hh:mm) (00:00 to 23:59)
p5 Timer operation (SINGLE, REPEAT)
If p2 is set to YEAR (month/day/time designation)
Syntax
TK p1,p2,p3,p4,p5,p6
p1 Timer number (1 to 4)
p2 Timer designation (YEAR)
p3 Month designation (JAN, FEB, MAR, APR,
MAY, JUN, JUL, AUG, SEP, OCT, NOV,
DEC)
p4 Day designation (1 to 31) The selectable
range varies on the specified month.
P5 Time (hh:mm) (00:00 to 23:59)
p6 Timer operation (SINGLE, REPEAT)
Example Specify 8:30 on April 28 every year for timer
number 3.
TK3,APR,28,08:30,REPEAT
Query
TK[ p1]?
Example Specify hour 21 every Thursday for timer number
2.
TK2,WEEK,THU,21:00,REPEAT
TU
Sets an event action
Syntax
TU p1,p2,p3,p4,p5,p6,p7
p1 Logic number (1 to 40)
p2 Event type
NONE
REMOTE
Remote control
RELAY
Alarm output relay
SWITCH
Internal switch
ALARM
Alarm occurrence
TIMER
Timer expiry
MATCHTIMETIMER
Match time expiry
USERKEY
USER key
p3 Event detail
p2
=REMOTE
Remote number (1 to
8)
p2
=RELAY
Relay number
p2
=SWITCH
Internal switch
number
p2
=TIMER
Timer number (1 to 4)
p2
=MATCHTIMETIMER Match timer number
(1 to 4)
p2
=Other
Space
p4 Action type
MEMORYSTART/STOP Start/stop sampling
MEMORYSTART
Start sampling
MEMORYSTOP
Stop sampling
TRIGGER
Event trigger
ALARMACK
Alarm acknowledge
MATHSTART/STOP Start/stop computation
MATHSTART
Start computation
MATHSTOP
Stop computation
MATHRESET
Reset computation
SAVEDISPLAY
Save display data to
an external storage
medium
SAVEEVENT
Save event data to an
external storage medium
MESSAGE
Write a message
SNAPSHOT
Take a snapshot
MANUALSAMPLE
Execute manual
sampling
TIMERRESET
Reset the relative timer
DISPLAYRATE1/2 Switch the trend
interval
DISPLAYGROUPCHANGE Switch the display group
FLAG
Raise a flag
TIMEADJUST
Synchronize the clock
PANELLOAD
Load settings
p5 Event detail 2
p4
=TIMERRESET Timer number (1 to 4)
p4
=DISPLAYGROUPCHANGE Group number
p4
=FLAG
Flag number (1 to 8)
p4
=MESSAGE
Message number (1 to
100)
p4
=PANELLOAD Setup file number (1 to
3)
p6 Event detail 3
p4
=MESSAGE
Method of specifying
the destination where
messages are written
ALL
All display groups
SELECT
A specified display
group
p7 Event detail 4
If p6 is set to
SELECT Group number
Some p4 parameters (action type) are not
selectable depending on p2 (event type).
Some p4 parameters (action type) are not
selectable depending on the settings or on the
installation of options.
Query
TU[ p1]?
Example Execute memory start with the remote control input
(terminal 1).
TUREMOTE,1,MEMORYSTART
Description Set parameter p3 (relay number, internal switch)
according to the table in section 4.3.
SK
Sets a computation constant
Syntax
SK p1,p2
p1 Constants number