3-14

IM MV1000-17E

Configuring the MV1000 Slave (Modbus Slave)

Configuring the Modbus Slave

◊ Press

MENU and then select Menu tab > Basic setting mode > Menu tab >

Communication (Serial) > Basic settings

Parameter

Setting

Address

1

Protocol

Modbus

* Set the communication parameters the same as those of the master device.

Configuring Measurement Channels

◊ Press

MENU and then select Menu tab > Meas channel > Range, Alarm

Parameter

Setting

First channel and last channel

1

Mode

Volt

Range

2V

Span_L

–2.0000

Span_U

2.0000

3.6 Usage Example of the Modbus Function