Tb sets the bar graph display, Sb sets the bar graph of a channel, Tn sets the scale – Yokogawa Button Operated MV2000 User Manual
Page 90: Sc sets a channel display color, Ta sets an alarm point mark
4-16
4.4 Setting Commands (Setting)
IM MV1000-17E
p3 Message display direction
HORIZONTAL
VERTICAL
p4 Scale display digits
NORMAL
3-digit display
FINE
4-digit display
p5 Current value display
MARK
Display using a mark
BARGRAPH
Display using a bar
graph
Query
TT?
Example Set the waveform to horizontal display and the
message direction to vertical, and display the
waveform by clearing the existing waveform at
memory start.
TTHORIZONTAL,ON,VERTICAL
SE
Sets the trend graph line width
and the number of grids
Syntax
SE p1,p2
p1 Trend line width (1 to 3) [dot]
p2 Number of grids (4 to 12, AUTO)
Query
SE?
Example Set the trend waveform line width to 1 dot and
the number of grids to 10.
SE1,10
TB
Sets the bar graph display
Syntax
TB p1
p1 Bar graph display direction
HORIZONTAL
VERTICAL
Query
TB?
Example Display the bar graph horizontally.
TBHORIZONTAL
SB
Sets the bar graph of a channel
Syntax
SB p1,p2,p3
p1 Measurement, computation, or external
input channel number
p2 Base position of the bar graph display
NORMAL Normal (lower limit)
CENTER
LOWER Lower limit
UPPER Upper limit
p3 Number of scale divisions (4 to 12)
Query
SB[ p1]?
Example Set the number of scale divisions of the channel
002 bar graph to 5, and display the bar graph
from the span lower limit (scale lower limit if
scaling is enabled).
SB002,NORMAL,5
Description You can specify a computation channel (or make
a query) on models with the /M1 math option.
You can specify an external input channel (or
make a query) on models with the /MC1 external
input channel option.
TN
Sets the scale
Syntax
TN p1,p2,p3
p1 Measurement, computation, or external
input channel number
p2 Display position (OFF, 1 to 10)
p3 Number of divisions (4 to 12, C10)
Query
TN[ p1]?
Example Set the channel 003 scale position to 2 and the
number of divisions to 10.
TN003,2,10
SV
Sets the moving average of a
measurement channel
Syntax
SV p1,p2,p3
p1 Measurement channel number
p2 Moving average ON/OFF
p3 Number of samples for computing the
moving average (2 to 400) [times]
Query
SV[ p1]?
Example Set the number of samples for computing the
moving average on channel 002 to 12.
SV002,12
SC
Sets a channel display color
Syntax
SC p1,p2
p1 Measurement, computation, or external
input channel number
p2 Display color (see SL (sets a trip line))
Query
SC[ p1]?
Example Set the channel 002 display color to blue.
SC002,BLUE
Description You can specify a computation channel (or make
a query) on models with the /M1 math option.
You can specify an external input channel (or
make a query) on models with the /MC1 external
input channel option.
TA
Sets an alarm point mark
Syntax
TA p1,p2,p3,p4,p5,p6,p7
p1 Measurement, computation, or external
input channel number
p2 Mark type
ALARM Alarm mark
FIXED Fixed mark
p3 Scale board display ON/OFF
p4 Alarm level 1 color (see SL (sets a trip line))
p5 Alarm level 2 color (see SL (sets a trip line))
p6 Alarm level 3 color (see SL (sets a trip line))
p7 Alarm level 4 color (see SL (sets a trip line))
Query
TA[ p1]?
Example Display alarm marks on the channel 004 scale.
TA004,ALARM,ON