App index, Xt sets the temperature unit, Rf sets the key lock function – Yokogawa Button Operated MV2000 User Manual
Page 105: Rn sets basic login settings, Rp sets login and user limitations, Ro sets report types and generation times
4-31
Commands
IM MV1000-17E
1
2
3
4
5
6
7
App
Index
XM
Sets the memory sample
condition
Syntax
XM p1
p1 Data type
DISPLAY Display data
EVENT Event data
E+D
Display data and event data
Query
XM?
Example Set the memory sampling condition to display
data.
XMDISPLAY
XT
Sets the temperature unit
Syntax
XT p1
p1 Temperature unit (C, F)
Query
XT?
Example Set the temperature unit to Celsius.
XTC
RF
Sets the key lock function
p1=KEY
Syntax
RF p1,p2,p3,p4,p5,p6,p7
p1 Type (KEY)
p2 START/STOP key (FREE, LOCK)
p3 HISTORY key (FREE, LOCK)
p4 MENU key (FREE, LOCK)
p5 USER key (FREE, LOCK)
p6 DISP/ENTER key (FREE, LOCK)
p7 T/DIV key (FREE, LOCK)
p1=FUNC (function keys)
Syntax
RF p1,p2,p3,p4,p5,p6,p7,p8
p1 Type (FUNC)
p2 Alarm acknowledge (FREE, LOCK)
p3 Message/batch (FREE, LOCK)
p4 Math (FREE, LOCK)
p5 Data save (FREE, LOCK)
p6 E-mail/FTP (FREE, LOCK)
p7 Time set (FREE, LOCK)
p8 Display function (FREE, LOCK)
p1=MEDIA (external storage media)
Syntax
RF p1,p2,p3
p1 Type (MEDIA)
p2 External storage media operation (FREE,
LOCK)
p3 Load setup (FREE, LOCK)
Query
RF[ p1]?
Example Lock the MENU key (leave other keys unlocked).
RFKEY,FREE,FREE,LOCK,FREE,FREE,FREE
RN
Sets basic login settings
Syntax
RN p1,p2
p1 Auto logout (OFF, 1MIN, 2MIN, 5MIN,
10MIN)
p2 Operation when logged out
OFF
Disable the MV operation
DISPLAY Allow only display-related
operations
Query
RN?
Example Set the auto logout time to 1 minute, and disable
the MV operation when logged out.
RN1MIN,OFF
RP
Sets login and user limitations
Syntax
RP p1,p2,···
p1 User limit number (1 to 10)
p2 User limit item (KEY, FUNC, MEDIA)
Description Parameters p3 and subsequent parameters vary
depending on the p2 setting as follows:
p2=KEY
p3 START/STOP key (FREE, LOCK)
p4 HISTORY key (FREE, LOCK)
p5 MENU key (FREE, LOCK)
p6 USER key (FREE, LOCK)
p7 DISP/ENTER key (FREE, LOCK)
p8 T/DIV key (FREE, LOCK)
p2=FUNC (function keys)
p3 Alarm acknowledge (FREE, LOCK)
p4 Message/batch (FREE, LOCK)
p5 Math (FREE, LOCK)
p6 Data save (FREE, LOCK)
p7 E-mail/FTP (FREE, LOCK)
p8 Time set (FREE, LOCK)
p9 Display function (FREE, LOCK)
Query
RP[ p1,[ p2]]?
Example Lock the START, HISTORY, and DISP/ENTER
keys.
RP1,KEY,LOCK,LOCK,,,LOCK
p2=MEDIA (external storage media)
Syntax
RP p1,p2,p3
p2 User limit item (MEDIA)
p3 External storage media operation (FREE,
LOCK)
p4 Load setup (FREE, LOCK)
Query
RP[p1]?
Example Limit access to the external storage medium and
the loading of setup data.
RPMEDIA,LOCK,LOCK
Description If key lock is enabled, setup data cannot be
loaded. You can place limitations on the loading
of setup data for users that are logged in.
RO
Sets report types and generation
times
To specify no report types
Syntax
RO p1
p1 Report type (OFF)
Query
RO?
4.6 Basic Setting Commands