Yokogawa Button Operated MV2000 User Manual
Page 49
IM MV1000-17E
2-34
Reading Data into External Input Channels (MV2000 only)
The MV reads the data from the server device and enters the data into external input
channels in 16-bit signed integer format.
• Example 1
Read a 16-bit unsigned integer value from instrument C’s register 30001 into external
input channel 201.
30001
201
16-bit unsigned integer
External input channel
Instrument C register
Command
R
201 - 201
3
30001
UINT16
• Example 2
Read a 32-bit unsigned integer value from instrument C’s register 32001 and 32002
into external input channel 202. Specify the smaller register number in the command.
32-bit unsigned integer
32001
32002
202
External input channel
Instrument C register
Higher bytes
Lower bytes
Command
R
202 - 202
3
32001
UINT32 _ B
Writing Measured Values to a Server
• Example
Write the measured value of channel 1 (16-bit signed integer) to instrument A’s
register 40001.
16-bit signed integer
Measurement channel
Instrument A register
001
40001
Command
W
001 - 001
1
40001
INT16
Writing Computed Values to a Server
• Example
Write the computed value of channel 101 (32-bit signed integer) to instrument A’s
40001 and 40002 registers, lower 16 bits first and then higher 16 bits. Specify the
smaller register number in the command.
32-bit signed integer
Computation channel
Instrument A register
101
Lower bytes
Higher bytes
40001
40002
Command
W-R
101 - 101
1
40001
INT32_L
2.9 Reading/Writing Data on Another Device from the MV via Modbus