App index, Xj sets an rjc, Wu sets environment settings – Yokogawa Button Operated MV2000 User Manual
Page 103
4-29
Commands
IM MV1000-17E
1
2
3
4
5
6
7
App
Index
Description Set parameter p1 according to the table in
section 4.3.
XJ
Sets an RJC
To use the internal compensation circuit
Syntax
XJ p1,p2
p1 Measurement channel number
p2 Reference junction compensation
designation (INTERNAL)
Query
XJ[ p1]?
Example Set the channel 001 RJC to the internal
compensation circuit.
XJ001,INTERNAL
To use an external RJC
Syntax
XJ p1,p2,p3
p1 Measurement channel number
p2 Reference junction compensation
designation (EXTERNAL)
p3 External RJC value (–20000 to 20000)
Query
XJ[ p1]?
Example Set the channel 002 RJC to external and set the
compensation value to 0 μV.
XJ002,EXTERNAL,0
Description • Set parameter p1 according to the table in
section 4.3.
• The unit of parameter p3 is μV.
WU
Sets environment settings
Setup items
GENERAL,BATCH,DISPLAY,MESSAGE,INPUT,
ALARM,SECURITY,MEDIA,MATH,REPORT,
SERVICEPORT,DECIMALPOINT,POP3
General environment settings
Syntax
WU p1,p2,p3
p1 Setting type (GENERAL)
p2 Tag/channel number selection
TAG
CHANNEL Channel number
p3 Language
ENGLISH
JAPANESE
CHINESE
GERMAN
FRENCH
KOREAN
Example Select tag display and set the language to
English.
WUGENERAL,TAG,ENGLISH
To set the batch function
Syntax
WU p1,p2,p3,p4
p1 Setting type (BATCH)
p2 Batch function ON/OFF
p3 Number of lot number digits (OFF, 4, 6, 8)
p4 Auto increment ON/OFF
Description Parameters p3 and p4 are valid only when p2 is
ON.
To set the display
Syntax
WU p1,p2
p1 Setting type (DISPLAY)
p2 Trend type (T-Y)
p3 Partial expansion ON/OFF
p4 Trend interval switching ON/OFF
To set message settings
Syntax
WU p1,p2,p3,p4
p1 Setting type (MESSAGE)
p2 Method of writing messages from keys
COMMON Applied to all display groups
SEPARATE Applied to a specified display
group
p3 Power failure message ON/OFF
p4 Change message ON/OFF
To set the input
Syntax
WU p1,p2
p1 Setting type (INPUT)
p2 Detection of values exceeding the scale
FREE
When the measurement range is
exceeded
OVER
When ±105% of the scale is
exceeded
To set alarm settings
Syntax
WU p1,p2
p1 Setting type (ALARM)
p2 Alarm suppression function ON/OFF
To set security settings
Syntax
WU p1,p2,p3
p1 Setting type (SECURITY)
p2 Keys
OFF
Disable security
KEYLOCK Lock the keys
LOGIN Enable the login function
p3 Communication
OFF
Disable security
LOGIN Enable the login function
Set media settings
Syntax
WU p1,p2,p3
p1 Setting type (MEDIA)
p2 Auto save function ON/OFF
p3 Media FIFO ON/OFF
Example Use media FIFO.
WUMEDIA,ON,ON
Description Parameter p3 is valid only when p2 is ON.
4.6 Basic Setting Commands