7-4

IM MV1000-17E

• Reading Values into External Input Channels (MV2000 only)

• External input channels are an MV2000 option (/MC1).
• Reads values from the server register into the MV external input channels.
• The data type of external input channels is 16-bit signed integer.
• The measurement range and unit are set on the external input channels. The

decimal place is determined by the external input channel’s span lower settings.

Register

Server

Data type

Read

R

MV2000

30001 to 39999

300001 to 365536

40001 to 49999

400001 to 465536

INT 16, UINT 16,

INT 32_B, INT 32_L,

UINT 32_B, UINT 32_L,

External Input data

Number: 201 to 440

Data type: 16-bit signed integer

Access

method

External Input Channel Values
The range of external input channel values is –30000 to 30000 after removing the

decimal. If a value is outside this range, the value is set to positive or negative range-
out.

Server Register Value

External Input Channel Value

Greater than 30000

Positive range-out (7FFFH)

–30000 to 30000

–30000 to 30000

Less than –30000

Negative range-out (8001H)

• Reading Values into Communication Input Channels

• Reads values from the server register into the MV communication input channels.
• Communication input data is an option (/M1 or /PM1).
• The data type of communication input data is 32-bit floating point.
• Communication input data can be displayed on a computation channel by writing

an expression that contains the data in an MV computation channel (/M1 or /PM1
option). The measurement range and unit are also set on a computation channel.

Register

Server

Data type

Read

R-M

MV1000 and MV2000

30001 to 39999

300001 to 365536

40001 to 49999

400001 to 465536

INT 16, UINT 16,

INT 32_B, INT 32_L,

UINT 32_B, UINT 32_L,

FLOAT_B, FLOAT_L

Communication input data

Number: C01 to C24 (MV1000)

C01 to C60 (MV2000)

Data type: 32-bit floating point

Access

method

• Writing Measured Values of Measurement Channels

• Writes measured values of measurement channels to server registers.
• The data type of measured values is 16-bit signed integer.

Access

method

Register

Server

Data type

W

40001 to 49999

400001 to 465536

INT 16,

FLOAT_B, FLOAT_L

Measurement channel

Number: 001 to 024 (MV1000)

001 to 048 (MV2000)

Data type: 16-bit signed integer

MV1000 and MV2000

Write

7.3 Modbus Protocol Specifications

This manual is related to the following products: