7-7

IM MV1000-17E

Specifications

1

2

3

4

5

6

7

App

Index

Input Register (shared with the Modbus slave function)

• Common Items

• The client device can only read the input registers.
• The readout data does not include decimal place and unit information. Specify them

on the client device.

• External input channels are an MV2000 option (/MC1).

• Details

Input Register

Data

Data Type

30001

Measured data of measurement channel 001 16-bit signed integer

|

|

30048

Measured data of measurement channel 048

• There is no decimal place information.

31001

Alarm status of measurement channel 001

Bit string

|

|

31048

Alarm status of measurement channel 048

• Register structure and alarm status values

2

1

4

3

4 bits

4 bits

4 bits

4 bits

4-bit value

Meaning

0

No alarm

1

High limit alarm

2

Low limit alarm

3

Difference high limit alarm

4

Difference low limit alarm

5

High limit on rate-of-change alarm

6

Low limit on rate-of-change alarm

7

Delay high limit alarm

8

Delay low limit alarm

Alarm level

Alarm status

32001

Lower word of the computed data of

computation channel 101

32-bit signed integer

32002

Higher word of the computed data of

computation channel 101

|

|

32119

Lower word of the computed data of

computation channel 160

32120

Higher word of the computed data of

computation channel 160

• Register structure

Channel 101 example

Higher word

Lower word

Register 32002

Computed data of channel 101

Register 32001

• There is no decimal place information.

33001

Alarm status of computation channel 101

Bit string

|

|

33060

Alarm status of computation channel 160

• Register structure and alarm status values: Same as those of measurement channels.

34001

Measured data of external input channel 201 16-bit signed integer

|

|

34240

Measured data of external input channel 440

• There is no decimal place information.
• The data in these registers are the data in the MV external input channels. If linear

scaling is enabled, the values are those after linear scaling.

35001

Alarm status of external input channel 201

Bit string

|

|

35240

Alarm status of external input channel 440

• Register structure and alarm status values: Same as those of measurement channels.

7.3 Modbus Protocol Specifications