beautypg.com

Sy sets the 4 panel display – Yokogawa Button Operated MV2000 User Manual

Page 96

background image

4-22

4.4 Setting Commands (Setting)

IM MV1000-17E

DHCP_LOG

DHCP log

MODBUS_LOG

Modbus log

SEPARATOR

If p2 is

4PANEL [select from the 5 items

below]
4PANEL1–4PANEL4 4 panel designation
SEPARATOR

Example Display SCALE and DIGITAL for the first and

second submenu items under the TREND main
menu item.
SM DISP_SUB,TREND,SCALE,DIGITAL

Description • Selectable items for p3 and subsequent

parameters vary depend on the p2 setting.

• If you omit parameters p3 and subsequent

parameters, all menus items will be hidden.

• A command error will occur if you specify the

same menu item multiple times.

• You can specify up to three separators. If you

specify more than three, an error will occur.

• You cannot specify EXPAND for LOG and

4PANEL.

• You cannot omit parameters by using

delimiters (, ,).

• If you execute SM DISP_SUB?, the MV also

transmits submenus of main menu items that
are turned Off.

• If you set the first menu item to SEPARATOR,

it will be ignored.

• The Show/Hide setting for the group

designation parameters, GROUP1 to
GROUP36, and the auto switching parameter,
AUTO, are applied universally to Trend,
Digital, Bar Graph, and Historical Trend. (For
example, if you set AUTO to Hide for Trend
and then set AUTO to Show for Digital, AUTO
will be set to Show for Trend, Digital, Bar
Graph, and Historical Trend.)

To set the function menu

p1

Type (FUNC)

p2–p28

Menu items to be displayed

The menu items for the functions you select

from below are displayed in the specified
order.

Only the specified menu items are displayed.

ALARMACK

Alarm acknowledge

MESSAGE
FREE_MESSAGE
TRIGGER

Event trigger

SAVE_DISPLAY

Save the display data

SAVE_EVENT

Save the event data

MANUAL_SAMPLE
SNAPSHOT
BATCH
MATH_START/STOP
MATH_RESET
MATH_ACK

Math data dropout
acknowledge

KEYLOCK

Enable/disable key
lock

LOGOUT
PASSWORD_CHANGE
EMAIL_START/STOP
EMAIL_TEST
FTP_TEST
SNTP
MEDIA_EJECT

Eject the storage
medium

SYSTEM_INFO

System information

NETWORK_INFO

Network information

TEXT_FIELD

Text field display

4PANEL
JUMP_DISPLAY

Register the home
display

RATE_CHANGE

Display rate 1/display
rate 2

FAVORITE_REGIST Register as favorite
SAVE_STOP

Stop the save
operation

TIMER_RESET
PAUSE_DISPLAY

Stop the monitor

LCD_SAVER

Backlight saver

MATCH_T_RESET

Reset the single
match timer

Example Display FREE MESSAGE and SNAPSHOT for

the first and second function menu items.
SMFUNC,FREE_MESSAGE,SNAPSHOT

Description • A command error will occur if you specify the

same menu item multiple times.

• You cannot specify SEPARATOR.
• You cannot omit parameters by using

delimiters (, ,).

• You cannot hide LOGOUT. If it is not included

in the parameters, it is displayed as the last
menu item.

Query

SM ?

To query all menu items

SM DISP_MAIN?

To query all main menu items

SM DISP_SUB?

To query all submenu items

SM DISP_SUB,TREND?

To query the Trend submenu items

SM FUNC?

To query all function menu items

SY

Sets the 4 panel display

Syntax

SY p1,p2,p3,p4,p5,p6,p7,p8,p9,p10,
p11
p1 1
p2 Screen number (1 to 4)
p3 Screen group name (up to 16 characters)
p4 Screen 1 type

TREND

Trend display

DIGITAL

Digital display

This manual is related to the following products: