Configuring the mv1000 client (modbus client) – Yokogawa Button Operated MV2000 User Manual
Page 57
IM MV1000-17E
2-42
Configuring the MV1000 Client (Modbus client)
The description below assumes that settings other than destination server settings and
commands are at default values.
Registering the Destination Server
The example below describes the settings used to register the MV1000 server to number 1.
The MV1000 server IP address is assumed to be 192.168.1.101.
◊ Press
MENU and then select Menu tab > Basic setting mode > Menu tab >
Communication (Ethernet) > Modbus client > Modbus server settings
Parameter
Setting
Port
502
Modbus server name
192.168.1.101
Unit
Auto
Setting Transmission Commands
◊ Press
MENU and then select Menu tab > Basic setting mode > Menu tab >
Communication (Ethernet) > Modbus client > Command settings
Parameter
Setting
Command type
R-M
First and Last
C01
Server
1
Regi.
30001
Type
INT16
2.10 Usage Example of the Modbus Function