App index, So sets a calculation expression, Er sets the range of an external input channel – Yokogawa Button Operated MV2000 User Manual
Page 85
4-11
Commands
IM MV1000-17E
1
2
3
4
5
6
7
App
Index
p8 Scaling decimal place (0 to 4)
p9 Unit (up to six alphanumeric characters)
p10 Low-cut function ON/OFF
p11 Low-cut point (0 to 50)
Query
SR[ p1]?
Example Convert the DC voltage measured on channel
001 to a flow rate using the square root
computation. Set the input range to 6 V, the span
lower limit to 1 V, the span upper limit to 5 V, the
scaling lower limit to 10.0 m
3
/s, and the scaling
upper limit to 100.0 m
3
/s.
SR001,SQRT,6V,1000,5000,100,1000,1,
m3/s
Description • You cannot execute this command while the
MV is measuring, computing, or generating a
report.
• Set parameters p1 and p3 according to the
table in section 4.3.
• For parameters p4 and p5, enter a value using
5 digits or less excluding the decimal point.
• Set all parameters p6, p7, and p8 or omit all
three parameters.
To set a channel to 1-5V DC input
Syntax
SR p1,p2,p3,p4,p5,p6,p7,p8,p9,p10
p1 Measurement channel number
p2 Input type(1-5V)
p3 Measurement range (1-5V)
p4 Span lower limit (800 to 5200)
p5 Span upper limit (800 to 5200)
p6 Scaling lower limit (–30000 to 30000)
p7 Scaling upper limit (–30000 to 30000)
p8 Scaling decimal place (0 to 4)
p9 Unit (up to six alphanumeric characters)
p10 Low-cut function ON/OFF
Query
SR[ p1]?
Example Set the channel 005 input type to 1-5V, the span
lower limit to 1 V, the span upper limit to 5 V, and
turn the 1-5V low-cut function ON.
SR005,1-5V,1-5V,1000,5000,,,,,ON
Description • You cannot execute this command while the
MV is measuring or computing.
• Set parameter p1 according to the table in
section 4.3.
• For parameters p4 and p5, enter a value using
4 digits or less excluding the decimal point.
• Set all parameters p6, p7, and p8 or omit all
three parameters.
SO
Sets a calculation expression
Syntax
SO p1,p2,p3,p4,p5,p6,p7
p1 Computation channel number
p2 Computation ON/OFF
p3 Calculation expression (up to 120
characters)
p4 Span lower limit (–9999999 to 99999999)
p5 Span upper limit (–9999999 to 99999999)
p6 Span decimal place (0 to 4)
p7 Unit (up to six alphanumeric characters)
Query
SO[ p1]?
Example Compute the sum of channels 001 and 002
on channel 106. Set the span lower limit to
–10.0000, the span upper limit to 15.0000, and
the unit to V.
SO106,ON,001+002,-100000,150000,4,V
Description • You can execute this command on models
with the /M1 math option.
• You cannot execute this command while the
MV is measuring or computing.
• For details on calculation expressions, see
section 2.2.
• Set parameter p1 according to the table in
section 4.3.
• For parameters p4 and p5, enter a value
using 7 digits or less excluding the decimal
for negative numbers and 8 digits or less for
positive numbers.
• Set all parameters p4, p5, and p6 or omit all
three parameters.
ER
Sets the range of an external
input channel
Syntax
ER p1,p2,p3,p4,p5,p6
p1 External input channel number
p2 External input channel ON/OFF
p3 Span lower limit (–30000 to 30000)
p4 Span upper limit (–30000 to 30000)
p5 Decimal place (0 to 4)
p6 Unit (up to six alphanumeric characters)
Query
ER[ p1]?
Example Set the span of external input channel 201 to
–150.00 to 150.00.
201,ON,-15000,15000,2
Description You can execute this command on models with
the /MC1 external input channel option.
TJ
Sets memory sampling
Syntax
TJ p1,p2
p1 Measurement, computation, or external
input channel number
p2 Memory sampling ON/OFF
Query
TJ[ p1]?
Example Save channel 002 to memory.
TJ002,ON
Description You can execute a computation channel (or
make a query) on models with the /M1 math
option. You can specify an external input channel
(or make a query) on models with the /MC1
external input channel option.
4.4 Setting Commands (Setting)