Data Dropout While Operating as a Modbus Master
If the MV tries to issue a command to a slave device but has not finished receiving
a response to the previous command, the MV will not be able to transmit the next
command. This will cause a data dropout. Take appropriate measures to prevent
dropouts by referring to the following figures.