Responses

1

2

3

4

5

6

7

App

Index

Ethernet Information

• The MV returns the Ethernet information in response to an FA command.

• Syntax

EACRLF
IP_Address______:xxx.xxx.xxx.xxxCRLF
Subnet_mask_____:xxx.xxx.xxx.xxxCRLF
Default_Gateway_:xxx.xxx.xxx.xxxCRLF
Primary_DNS_____:xxx.xxx.xxx.xxxCRLF
Secondary_DNS___:xxx.xxx.xxx.xxxCRLF
Host____________:yyy······CRLF
Domain__________:zzz······CRLF
ENCRLF

xxx IP address number (000 to 255)
yyy··· Host name (up to 64 characters)
zzz··· Domain name (up to 64 characters)

File List

• The MV returns the file list or the file data sizes for the specified directory on the MV’s

external storage medium in response to the ME command.

• Syntax

EACRLF
yy/mo/dd_hh:mm:ss_ssssssss_fff···_0_xxx···CRLF
··············································
ENCRLF

yy Year (00 to 99)
mo Month (01 to 12)
dd Day (01 to 31)
hh Hour (00 to 23)
mm Minute (00 to 59)
ss Second (00 to 59)
ssssssssss Data size of the file (_______0 to 99999999) [byte(s)]
fff··· File name (51 characters including the extension. If it is less than

51, spaces are entered.)

If this is a directory, the characters

are shown at the

position displaying the file data size.

xxx··· Data serial number (16-digit hexadecimal)
_ Space

The data serial number is included for files in the DATA directory in the internal

memory. For other files, the data serial number is spaces.