4 setting commands (setting), 4 setting commands (setting) -10, Sr sets an input range – Yokogawa Button Operated MV2000 User Manual
Page 84
4-10
4.4
Setting Commands (Setting)
IM MV1000-17E
4.4 Setting Commands
(Setting)
SR
Sets an input range
To set a channel to skip
Syntax
SR p1,p2
p1 Measurement channel number
p2 Setting type (SKIP)
Query
SR[ p1]?
Example Skip channel 001.
SR001,SKIP
Description • You cannot execute this command while the
MV is measuring or computing.
• A channel set to SKIP is not measured.
• Set parameter p1 according to the table in
section 4.3.
To set a channel to voltage, TC, RTD, or ON/OFF
input
Syntax
SR p1,p2,p3,p4,p5
p1 Measurement channel number
p2 Input type
VOLT
DC voltage
TC
Thermocouple
RTD
RTD
DI
ON/OFF input
p3 Measurement range
p4 Span lower limit
p5 Span upper limit
Query
SR[ p1]?
Example Set the channel 001 input type to TC type R, the
span lower limit to 0°C, and the span upper limit
to 1760.0°C.
SR001,TC,R,0,17600
Description • You cannot execute this command while the
MV is measuring, computing, or generating a
report.
• Set parameters p1 and p3 according to the
table in section 4.3.
• For parameters p4 and p5, enter a value using
5 digits or less excluding the decimal point.
To set a channel to difference computation
Syntax
SR p1,p2,p3,p4,p5,p6,p7
p1 Measurement channel number
p2 Setting type (DELTA)
p3 Input type
VOLT
DC voltage
TC
Thermocouple
RTD
RTD
DI
ON/OFF input
p4 Measurement range
p5 Span lower limit
p6 Span upper limit
p7 Reference channel number (measurement
channel number)
Query
SR[ p1]?
Example Set the channel 010 setting type to differential
computation between channels with the reference
channel set to 001, and set the input type to TC.
Set the measurement range to R. Set the span
lower limit to 10.0°C and span upper limit to 100.0°C.
SR010,DELTA,TC,R,100,1000,001
Description • You cannot execute this command while the
MV is measuring, computing, or generating a
report.
• Set parameters p1 and p4 according to the
table in section 4.3.
• For parameters p5 and p6, enter a value
using 5 digits or less excluding the decimal
point.
To set a channel to scaling
Syntax
SR p1,p2,p3,p4,p5,p6,p7,p8,p9,p10
p1 Measurement channel number
p2 Setting type (SCALE)
p3 Input type
VOLT
DC voltage
TC
Thermocouple
RTD
RTD
DI
ON/OFF input
p4 Measurement range
p5 Span lower limit
p6 Span upper limit
p7 Scaling lower limit (–30000 to 30000)
p8 Scaling upper limit (–30000 to 30000)
p9 Scaling decimal place (0 to 4)
p10 Unit (up to six alphanumeric characters)
Query
SR[ p1]?
Example Convert the DC voltage measured on channel
002 to DC current. Set the input range to 6 V,
the span lower limit to 1 V, the span upper limit
to 5 V, the scaling lower limit to 1.00 A, and the
scaling upper limit to 5.00 A.
SR002,SCALE,VOLT,6V,1000,5000,100,5
00,2,A
Description • You cannot execute this command while the
MV is measuring, computing, or generating a
report.
• Set parameters p1 and p4 according to the
table in section 4.3.
• For parameters p5 and p6, enter a value
using 5 digits or less excluding the decimal
point.
• Set all parameters p7, p8, and p9 or omit all
three parameters.
To set a channel to square root computation
Syntax
SR p1,p2,p3,p4,p5,p6,p7,p8,p9,p10,p11
p1 Measurement channel number
p2 Setting type (SQRT)
p3 Measurement range
p4 Span lower limit
p5 Span upper limit
p6 Scaling lower limit (–30000 to 30000)
p7 Scaling upper limit (–30000 to 30000)