beautypg.com

Yokogawa Button Operated MV2000 User Manual

Page 71

background image

3-12

IM MV1000-17E

• Communication Conditions

The read cycle, Inter-block delay, Time out, Auto recovery, and Retrials settings are

displayed.

• Communication Status

The MV displays the communication status using status lamps and detail codes.

Status Lamp

Detail Code Meaning

Green

Good

Communication is operating normally.

Yellow

Command is readying.

Red

Communication is stopped.

Common to yellow and red None

No response from the slave device.

Func

The slave device cannot execute the command

from the MV.

Regi

The slave device does not have the specified

register.

Err

There is an error in the response data from the

slave device (communication error).

(Space)

The detail code does not appear until the status

is confirmed when communication is started.

Resuming Command Transmission

Using the front panel keys, you can resume command transmission to a slave device
whose communication is stopped (red status lamp).

1.

Using the up and down arrow keys, select the command assigned to the slave

device that you want to resume transmission. The message “Push [right arrow]
key to refresh” appears.

2.

Press the right arrow key. The MV will transmit a command to the specified slave

device.

Data during Connection Retrials

On a Modbus master, the communication input data and external input channel data
are held at the previous values while the command is being retried. If the command
transmission stops, the status lamp will turn red, and the communication input data and
external input channel data will be error data. For computation channels, the MV displays
“+OVER” or “–OVER” according to the settings. The MV displays “******” for external
input channels.

Data Dropout

A data dropout occurs when the commands 1 to 16 do not complete within the read cycle
(see appendix 2). When a data dropout occurs, the communication input data is held at
the previous value. The Modbus status display shows a message indicating that a data
dropout occurred. If this happens, take measures such as making the read cycle longer
or reducing the number of commands. Be sure to confirm that no data dropout occurs on
the Modbus status log display.

3.5 Reading/Writing Data on Another Device from the MV via Modbus

This manual is related to the following products: