4
5
6
7
App
Index
4.10 Output Commands (Special
Response Commands)
*I
Transmits instrument
information
Syntax
*I
Description Transmits the maker, model, serial number, and
firmware version in a comma-separated ASCII
text with a terminator at the end.
Example
YOKOGAWA,MV1000,99AA0123,F1.01
4.11 Maintenance/Test
Commands (available when
using the maintenance/
test server function via the
Ethernet interface)
close Disconnects the connection
between other instruments
Syntax
close,p1,p2:p3
p1 MV port (1 to 65535)
p2 PC IP address
(0.0.0.0 to 255.255.255.255)
p3 PC port (0 to 65535)
Example
close,34159,192.168.111.24:1054
E0
Description You cannot use this command to disconnect
a server port. You cannot use this command
to disconnect a port of an instrument that is
being controlled. Use the quit command for this
purpose.
con
Transmits connection
information
Syntax
con
Example
con
EA
00/00/00 12:34:56
Active connections
Proto Local Address Foreign Address State
TCP 192.168.111. 24:34159 192.168.111. 24:1053 ESTABLISHED
TCP 0. 0. 0. 0:34155 0. 0. 0. 0:
0 LISTEN
TCP 0. 0. 0. 0:34159 0. 0. 0. 0:
0 LISTEN
TCP 0. 0. 0. 0:34150 0. 0. 0. 0:
0 LISTEN
EN
TCP
The protocol used.
Local Address
The MV socket address.
Displays “IP address:port number.”
Foreign Address
The destination socket address.
Displays “IP address:port number.”
State
Connection state.
ESTABLISHED
Connection established.
eth
Transmits Ethernet statistics
Syntax
eth
Example
eth
EA
00/00/00 12:34:56
4.10 Output Commands (Special Response Commands)/