2 device address setting, 1 multidrop mode canceling, 2 multidrop mode setting – Yokogawa FieldMate User Manual

Page 81: Device address setting -3 9.2.1, Multidrop mode canceling -3, Multidrop mode setting -3, Warning

background image

<9 COMMUNICATION ERROR>

9-3

IM 01R01A11-01EN

9.2

Device Address Setting

WARNING

This operation must be carried out by the trained personnel having knowledge of multidrop loop.

For the details of the parameter setting procedure, refer to IM 01E20C01-01E or IM 01E20C02-

01E. After using Verification Tool, set the AXF to the original multidrop loop.

9.2.1

Multidrop Mode Canceling

F090201-A.ai

USB FieldMate Modem

Device A

Device Address: 1

Device B

Device Address: 2

Device C

Device Address: 3

Device X

Device Address: 15

Load: 250 Ω

+

-

+

-

+

-

+

-

USB FieldMate Modem

Device A

Device Address: 1

Load: 250 Ω

Load:

250 Ω

Multidrop Loop side

+

-

Set to “0”.

F090201-B.ai

(A) Multidrop loop

(B) After canceling Multidrop loop

Figure 9.2.1 Configuration

1) Disconnect the target device (AXF) from the multidrop loop physically.
2) Connect the AXF to FieldMate one to one. A load of 250Ω is required. See

Figure 9.2.1 (B).

3) Record the following original AXF parameter, and then set the parameter as shown.

Table 9.2.1 Parameter of Cancelling Multidrop mode

HART Parameter (DTM)

Setting Value

Poll Addr

Configuration → HART → Poll addr

0

4) Start Verification Tool.

9.2.2

Multidrop Mode Setting

After using Verification Tool, set the AXF back to its original status.
1) After Verification Tool termination, set the AXF parameter back to its original value manually.

Table 9.2.2 Parameter Setting of Multidrop mode

HART Parameter (DTM)

Setting Value

Poll Addr

Configuration → HART → Poll addr

Original Value

2) Connect the AXF back to the original configuration.