beautypg.com

1 current output, Current output -25 – Yokogawa FieldMate User Manual

Page 57

background image

<6 OPERATION>

6-25

IM 01R01A11-01EN

6.3.1

Current Output

This item checks the current output from the converter.

3

1

2

4

F060302.ai

Figure 6.3.2 “Current Output” Screen

Table 6.3.2 “Current Output” Screen

Item

No.

Item Name

Description

1

Connection diagram

Shows the connection diagram on another screen. See

Figure 6.3.3.

2

Measured (mA)

Enter the measured value manually.

3

Output (*1)

in Output Selection

Outputs the current.

By clicking “Output” after selecting each setting value, the preferred cur-

rent is transferred to AXF.

(Only when Verifi cation Tool is in “online” mode)

4

Exit

in Output Selection

Stops the current output and enables other operations.

(Only when Verifi cation Tool is in “online” mode)

*1: When the AXF protect function is set to “Protect”,

Figure 3.2.2 is displayed after clicking “Output”. Follow 3.2.2.