Yokogawa FieldMate User Manual
Page 45
<6 OPERATION>
6-13
IM 01R01A11-01EN
2
3
4
5
6
7
1
F060202.ai
Figure 6.2.2 “Circuit and Device Status” Screen
Table 6.2.2 “Circuit and Device Status” Screen
(1) Nominal size is 400mm or smaller, without optional code ELC
Item
No.
Item Name
Description
Check is [possible/ not available]
No Flow
Flow
No Flow +
Flow
1
No Flow
Flow
Shows test condition.
Select the test condition
2
Test Condition
Shows operated test condition.
“No Flow” or ” Flow” or ” No Flow
+ Flow”
See Figure 6.2.13.
3
Circuit
Magnetic
Circuit
Shows the result of the
Magnetic Circuit check.
“Magnetic Circuit” means check-
ing the magnetic circuit inside the
flowtube.
Possible
Not Avail-
able
[Shows: N/A]
Possible
4
Excitation
Circuit
Shows the result of the
Excitation Circuit check.
“Excitation Circuit” means check-
ing the excitation circuit by the
excitation current measurement.
Possible
Possible
Possible
5
Calculation
Circuit
Shows the result of the
Calculation Circuit check.
“Calculation Circuit” means check-
ing the operation circuit which
calculates the flow velocity.
Not Avail-
able
[Shows :N/A]
Possible
Possible
6
Device
Status
Alarm
Check
Shows the result of the Alarm
Check.
“Alarm Check” means checking
the occurrence of alarms.
Possible
Possible
Possible
7
Alarm
History
Shows the result of Alarm History
Check.
“Alarm History Check” means
checking the history of alarms that
occurred.
Possible
Possible
Possible