<10. General Specifications>
10-3
IM 01C25R03-01E
Item
Description
Code
Canadian
Standards
Association
(CSA)
CSA Explosionproof
*2
Certificate: 2014354
Applicable Standard: C22.2 No.0, C22.2 No.0.4, C22.2 No.0.5, C22.2 No.25, C22.2 No.30,
C22.2 No.94, C22.2 No.60079-0, C22.2 No.60079-1, C22.2 No.61010-1-01
Explosion-proof for Class I, Groups B, C and D.
Dustignition-proof for Class II/III, Groups E, F and G.
When installed in Division 2, “SEAL NOT REQUIRED” Enclosure: TYPE 4X, Temp. Code:
T6...T4
Ex d IIC T6...T4 Enclosure: IP66 and IP67
Max.Process Temp.: T4; 120°C (248°F), T5; 100°C (212°F), T6; 85°C (185°F)
Amb.Temp
*1
.: –50 to 75°C (–58 to 167°F) for T4, –50 to 80°C (–58 to 176°F) for T5,
–50 to 75°C (–58 to 167°F) for T6
CF1
CSA Intrinsically Safe
*3
—
IECEx
Scheme
*2
IECEx Flameproof
Applicable Standard: IEC 60079-0:2004, IEC60079-1:2003
Certificate: IECEx CSA 07.0008
Flameproof for Zone 1, Ex d IIC T6...T4 Enclosure: IP66/IP67
Max.Process Temp.: T4; 120°C (248°F), T5; 100°C (212°F), T6; 85°C (185°F)
Amb.Temp
*1
.: –50 to 75°C (–58 to 167°F) for T4, –50 to 80°C (–58 to 176°F) for T5,
–50 to 75°C (–58 to 167°F) for T6
SF2
*1:
Lower limit of ambient temperature shall be -15ºC (5ºF) when /HE is specified.
*2:
Applicable for electrical connection code
2, 4, 7, 9, C and D.
*3:
Pending.
< Factory Setting >
Tag Number (Tag plate)
As specified in order
Software Tag (PD_TAG)
‘FT1001’ unless otherwise both Tag Number and Software Tag
specified in order
Node Address
‘0xF5’ unless otherwise specified in order
Operation Functional Class
‘BASIC’ or as specified
Primary value
*1
Output Mode (L_TYPE)
‘Direct’ unless otherwise specified in order
Calibration Range (XD_SCALE)
Lower/Higher Range Value
As specified in order
Calibration Range Unit
Selected from mmH
2
O, mmH
2
O(68°F), mmHg, Pa, hPa, kPa,
MPa, mbar, bar, gf/cm
2
, kgf/cm
2
, inH
2
O, inH
2
O(68°F), inHg, ftH
2
O,
ftH
2
O(68°F) or psi. (Only one unit can be specified)
Output Scale (OUT_SCALE)
Lower/Higher Range Value
‘0 to 100%’ unless otherwise specified.
Software Damping
*2
‘2 seconds’ or as specified in order
Static pressure display range
‘0 to 25 MPa’ for EJX910A M and H capsule and ‘0 to 16 MPa’ for
EJX910A L capsule, absolute value.
‘0 to 32 MPa’ for EJX930A. Measuring high pressure side.