5 setting parameters with using dtm, 6 reading the parameters, 7 continuous record of values – Yokogawa EJX930A User Manual
Page 27: 8 generation of alarm, Setting parameters with using dtm -4, Reading the parameters -4, Continuous record of values -4, Generation of alarm -4
<4. Getting Started>
4-4
IM 01C25R03-01E
4.5 Setting Parameters with
Using DTM
When setting parameters with using FieldMate
(a software for configuring and adjusting the field
devices), please use applicable DTM (Device Type
Manager) listed in below.
Table 4.2
DTM
DTM
EJX Multivariable Transmitters
Name
Model
Device Type
Device
Revision
EJX910
V2.1
EJX910A
EJX930A
EJX910
(0x000E)
2
4.6 Reading the Parameters
To read EJX multivariable transmitter parameters,
select the AI1 block of the transmitter from the host
screen and read the OUT parameter. The current
selected signal is displayed. Check that MODE_
BLOCK of the function block and resource block
is set to AUTO, and change the signal input and
read the parameter again. A new designated value
should be displayed.
4.7 Continuous Record of
Values
If the host has a function that continuously
records the indications, use this function to list the
indications (values). Depending on the host being
used, it may be necessary to set the schedule of
Publish (the function that transmits the indication on
a periodic basis).
4.8 Generation of Alarm
Generation of an alarm can be attempted from
EJX multivariable transmitter. Block alarm, Output
limit alarm, and Update alarm are informed to the
host. When generating alarm, a Link Object and a
VCR Static Entry need to be set. For details of Link
Object and VCR Static Entry, refer to section 5.6.1
Link object and section 5.5.1 VCR Setting.