<6. Explanation of Basic Items>

6-6

IM 01C25R03-01E

A preset fixed value can be output to the AI function

block or FLOW transducer block instead of the

differential pressure value, static pressure value

and external temperature value calculated from the

sensor signals.
Select the signal for enabling simulation in the

SIMULATE_MODE parameter. Set the value and

status to be used for simulation in the SIMULATE_

DPRESS, SIMULATE_SPRESS, and SIMULATE_

ETEMP parameters.

Parameter

Explanation

SIMULATE_
MODE

Select the signal for enabling simulation.

0= Simulation OFF

1= Differential pressure signal

simulation ON

2= Static pressure signal simulation ON

3= Differential pressure signal + static

pressure signal simulation ON

4= External temperature signal

simulation ON

5= Differential pressure signal +

external temperature signal simulation

ON

6= Static pressure signal + external

temperature signal simulation ON

7= Differential pressure signal +

static pressure signal + external

temperature signal simulation ON

15=Differential pressure signal +

static pressure signal + external

temperature signal (w/out damping

processing) simulation ON

SIMULATE_
DPRESS

Set the differential pressure signal

simulation value and status.

SIMULATE_
SPRESS

Set the static pressure signal simulation

value and status.

SIMULATE_
ETEMP

Set the external temperature signal

simulation value and status.

The flow value becomes the simulation value

which is calculated by using simulation value of

DP, SP and ET. The LCD continuously displays the

simulation value and alarm (AL.080 SNR.SIM) in

alternating sequence.
Simulation continues for 10 minutes, then is

released automaticaly.
If one of following alarm occurs, all the output data

is hold to the value before alarm occurs.

AL.01 (CAP. ERR)

AL.02 (AMP. ERR)

AL.03 (ET. ERR)

The simulation mode will automatically be released

after approximately ten minutes.

NOTE

If the DP or SP simulation value set by a user is

out of the setting range of the product(capsule),

the transmitter automatically use maximum or

minimum settable value in place of actual setting

value to perform simulation.

If the ET simulation value set by a user is out of

the setting range, a configuration error occurs.

6.3.7 Functions Relating to Capsule and

Amplifier Temperature

Reference to capsule and amplifier temperature

value:

In CAP_TEMP_VAL and AMP_TEMP_VAL, it

is possible to refer to the capsule and amplifier

temperature value and status. The update period

of this value is about 1 second. The temperature

unit is selected by XD_SCALE.unit of the AI block,

in which CAP_TEMP_VAL is selected. The status

is normally Good-Non Specific. However, in the

case of sensor failure or out of measurement range,

it turns to Bad or Uncertain. For specifics, refer to

Table 8.9.
Determination of the range limit of capsule

temperature:

The range of capsule temperature is from -40 to

120°C. When the measured capsule temperature

deviates from -50 to 130°C range, set the status of

CAP_TEMP_VAL to Uncertain-Sensor Conversion

not Accurate. The status under normal conditions

is Good-Non Specific. Also, set the status of

PRIMARY_VALUE, SECONDARY_VALUE and

TERTIARY_VALUE TO Uncertain-Subnormal.
Determination of the range limit of amplifier

temperature:

The range of amplifier temperature is from -40 to

120°C. When the measured amplifier temperature

deviates from -50 to 95°C range, set the status of

AMP_TEMP_VAL to Uncertain-Sensor Conversion

not Accurate. The status under normal conditions is

Good-Non Specific.