<6. Explanation of Basic Items>

6-16

IM 01C25R03-01E

F0609.ai

ALARM_OPTS=HI_HI

|

HI

|

LO_LO

(A case of HI_HI, HI and LO_LO options are selected)

HI_HI_LIM
HI_LIM

LO_LO_

LIM

OUT_D.value = 0

OUT_D.value = 1

OUT_D.value = 1 OUT_D.value = 1

OUT_D.value = 1

Figure 6.6

An Example of OUT_D.value

6.6.6 Basic Parameters of the AI Block.

Parameter

Outline

OUT

Shows output value and status. When the Block mode is Man and O/S, the value is held.

SIMULATE

Used for simulation. It sets the value and status arbitrarily from the transducer. Use this parameter for

loop checking. Refer to 7.3 Simulation Function.

XD_SCALE

Sets the range of inputs from the transducer block that corresponds to 0% and 100% in the AI function

block. Also sets the unit of the range, inputs values that correspond to 0% and 100%, and four decimal

values.

OUT_SCALE Sets the range, unit, and digit of the output scale.
CHANNEL

Selects the signal which is calculated in SENSOR Transducer Block. The relation between the signals

and channels are shown below;

Channel 1: PRIMARY_VALUE (pressure/differential pressure)

Channel 2: SECONDARY_VALUE (H-side static pressure)

Channel 3: TERTIARY_VALUE (L-side static pressure)

Channel 4: EXT_TEMP_VALUE(external temperature)

Channel 5: FLOW_VALUE(flow)

Channel 6: CAP_TEMP_VAL (capsule temperature)

Channel 7: AMP_TEMP_VAL (amplifier temperature)

Channel 8: FLG_TEMP_VAL (flange temperature, option code: /DG1)

Flow value(channel 5) can be assigned to only one AI block at one time.

Other variables can be assigned to one or more AI blocks simultaneously.

L_TYPE

The operation function of the AI function block can be selected from Direct, Indirect Linear, or Indirect

SQRT:

Direct: The Signal from the transducer block is directly output by filtering only, but without scaling or

square root extraction.

Indirect Linear: Values scaled according to the range settings of XD_SCALE and OUT_SCALE are

output.

Indirect SQRT: The square root extraction is performed to the values scaled according to the range

settings of XD_SCALE. The square root values are scaled and output according to the range settings

of OUT_SCALE.

LOW_CUT

When the output value is smaller than the value set by this parameter, the output value is 0. To enable

the low-cut function, this parameter must be enabled in IO_OPTS. The setting is in an engineering unit of

OUT_SCALE. 1% of OUT_SCALE is applied as hysteresis.