A8.3.6 Status Error
There are three statuses of “GOOD”,
“UNCERTAIN”, and “BAD” for the status of FLG_
TEMP_VAL.
The factor that becomes GOOD/UNCERTAIN/BAD
is as follows.
Good: Normal status
Uncertain: Capsule or Amplifier temperature is
out of range
Bad:
• Capsule or Amplifier temperature sensor
failure
• Capsule or Amplifier EEPROM failure
• Resource block or SENSOR Transducer
block is in O/S mode
A8.3.7 Parameter Lists for Heat Trace
Monitoring Function
All the parameters for Heat Trace Monitoring
function belong to the SENSOR Transducer block.
Relative
Index Index
Parameter Name
Factory Default Write
Mode
Explanation
64
2064 CAP_TEMP_VAL
—
Measured capsule temperature value and status.
65
2065 CAP_TEMP_RANGE -50.0 to 130.0°C
—
High and low range limit values, engineering units, decimal point
place for capsule temperature.
66
2066 AMP_TEMP_VAL
—
Measured Amplifier temperature value and status.
67
2067 AMP_TEMP_RANGE -50.0 to 95.0°C
—
High and low range limit values, engineering units, decimal point
place for Amplifier temperature.
114
2114 FLG_TEMP_VAL
(Note)
—
Calculated flange temperature valueand status.
115
2115 FLG_TEMP_RANGE
-50.0 to 130.0°C
—
High and low range limit values, engineering units, decimal point
place for flange temperature.
116
2116 FLG_TEMP_COEFF
0
AUTO Coefficient to calculate flange temperature.
117
2117 FLG_TEMP_PRI
1
AUTO Priority of the flange temperature alarm. (Not used)
118
2118 FLG_TEMP_H_LIM
130
AUTO Threshold to generate Flg Temp High Alarm.
119
2119 FLG_TEMP_L_LIM
-50
AUTO Threshold to generate Flg Temp Low Alarm.
120
2120 FLG_TEMP_ALM
—
Status of flange temperature alarm.
Note: The factory default of FLG_TEMP_COEF is 0 so the factory default of FLG_TEMP_VAL indicates the same value as that of
CAP_TEMP_VAL.