A8.3.6 Status Error

There are three statuses of “GOOD”,

“UNCERTAIN”, and “BAD” for the status of FLG_

TEMP_VAL.
The factor that becomes GOOD/UNCERTAIN/BAD

is as follows.

Good: Normal status

Uncertain: Capsule or Amplifier temperature is

out of range

Bad:

• Capsule or Amplifier temperature sensor

failure

• Capsule or Amplifier EEPROM failure

• Resource block or SENSOR Transducer

block is in O/S mode

A8.3.7 Parameter Lists for Heat Trace

Monitoring Function

All the parameters for Heat Trace Monitoring

function belong to the SENSOR Transducer block.

Relative

Index Index

Parameter Name

Factory Default Write

Mode

Explanation

64

2064 CAP_TEMP_VAL

Measured capsule temperature value and status.

65

2065 CAP_TEMP_RANGE -50.0 to 130.0°C

High and low range limit values, engineering units, decimal point

place for capsule temperature.

66

2066 AMP_TEMP_VAL

Measured Amplifier temperature value and status.

67

2067 AMP_TEMP_RANGE -50.0 to 95.0°C

High and low range limit values, engineering units, decimal point

place for Amplifier temperature.

114

2114 FLG_TEMP_VAL

(Note)

Calculated flange temperature valueand status.

115

2115 FLG_TEMP_RANGE

-50.0 to 130.0°C

High and low range limit values, engineering units, decimal point

place for flange temperature.

116

2116 FLG_TEMP_COEFF

0

AUTO Coefficient to calculate flange temperature.

117

2117 FLG_TEMP_PRI

1

AUTO Priority of the flange temperature alarm. (Not used)

118

2118 FLG_TEMP_H_LIM

130

AUTO Threshold to generate Flg Temp High Alarm.

119

2119 FLG_TEMP_L_LIM

-50

AUTO Threshold to generate Flg Temp Low Alarm.

120

2120 FLG_TEMP_ALM

Status of flange temperature alarm.

Note: The factory default of FLG_TEMP_COEF is 0 so the factory default of FLG_TEMP_VAL indicates the same value as that of

CAP_TEMP_VAL.