Parameter lists, 1 resource block, Parameter lists -1 – Yokogawa EJX930A User Manual
Page 65: Resource block -1
<9. Parameter Lists>
9-1
IM 01C25R03-01E
9. Parameter Lists
Note: The Write Mode column contains the modes in which each parameter is write enabled.
O/S: Write enabled in O/S mode.
MAN: Write enabled in Man mode and O/S mode.
AUTO: Write enabled in Auto mode, Man mode, and O/S mode.
9.1 Resource Block
Relative
Index Index
Parameter Name
Factory Default
Write
Mode
Explanation
0
1000 Block Header
TAG:“RS”
Block
Tag=O/S
Information on this block such as Block Tag, DD Revision,
Execution Time etc.
1
1001 ST_REV
—
—
The revision level of the static data associated with the resource
block. The revision value is incremented each time a static
parameter value in this block is changed.
2
1002 TAG_DESC
Null
AUTO
The user description of the intended application of the block.
3
1003 STRATEGY
1
AUTO
The strategy field can be used to identify grouping of blocks.
This data is not checked or processed by the block.
4
1004 ALERT_KEY
1
AUTO
The identification number of the plant unit. This information may
be used in the host for sorting alarms, etc.
5
1005 MODE_BLK
AUTO
AUTO
The actual, target, permitted, and normal modes of the block.
6
1006 BLOCK_ERR
—
—
This parameter reflects the error status associated with the
hardware or software components associated with a block. It is
a bit string, so that multiple errors may be shown.
7
1007 RS_STATE
—
—
State of the resource block state machine.
8
1008 TEST_RW
Null
AUTO
Read/write test parameter-used only for conformance testing
and simulation.
9
1009 DD_RESOURCE
Null
—
String identifying the tag of the resource which contains the
Device Description for this resource.
10
1010 MANUFAC_ID
0x00594543
—
Manufacturer identification number-used by an interface device
to locate the DD file for the resource.
11
1011 DEV_TYPE
14 (0x000E)
—
Manufacturer’s model number associated with the resource-
used by interface devices to locate the DD file for the resource.
12
1012 DEV_REV
2
—
Manufacturer revision number associated with the resource-
used by an interface device to locate the DD file for the
resource.
13
1013 DD_REV
1
—
Revision of the DD associated with the resource-used by an
interface device to locate the DD file for the resource.
14
1014 GRANT_DENY
0
AUTO
Options for controlling access of host computer and local control
panels to operating, tuning and alarm parameters of the block.
15
1015 HARD_TYPES
Scalar input
—
The types of hardware available as channel numbers.
bit0: Scalar input
bit1: Scalar output
bit2: Discrete input
bit3: Discrete output
16
1016 RESTART
—
—
Allows a manual restart to be initiated. Several degrees of
restart are possible. They are 1: Run, 2: Restart resource, 3:
Restart with initial value specified in FF functional spec. (*1),
and 4: Restart processor.
*1: FF-891 Foundation
TM
Specification Function Block
Application Process Part 2.
17
1017 FEATURES
Soft write lock
supported Report
supported
—
Used to show supported resource block options.
18
1018 FEATURE_SEL
Soft write lock
supported Report
supported
AUTO
Used to select resource block options defined in FEATURES.
bit0: Scheduled
bit1: Event driven
bit2: Manufacturer specified
19
1019 CYCLE_TYPE
Scheduled
—
Identifies the block execution methods available for this
resource.
20
1020 CYCLE_SEL
Scheduled
AUTO
Used to select the block execution method for this resource.
21
1021 MIN_CYCLE_T
3200 (100ms)
—
Time duration of the shortest cycle interval of which the
resource is capable.