beautypg.com

Yokogawa EJX930A User Manual

Page 21

background image

<2. Handling Cautions>

2-10

IM 01C25R03-01E

Note 2. Wiring

• In hazardous locations, the cable entry

devices shall be of a certified flameproof

type, suitable for the conditions of use and

correctly installed.

• Unused apertures shall be closed with

suitable flameproof certified blanking

elements.

Note 3. Operation

• WARNING:

AFTER DE-ENERGIZING, DELAY 5

MINUTES BEFORE OPENING.

• WARNING:

WHEN AMBIENT TEMPERATURE ≥ 65ºC,

USE THE HEAT-RESISTING CABLES ≥

90ºC.

• Take care not to generate mechanical

sparking when accessing to the instrument

and peripheral devices in a hazardous

location.

Note 4. Maintenance and Repair

• The instrument modification or parts

replacement by other than authorized

representative of Yokogawa Electric

Corporation is prohibited and will void IECEx

Certification.