A6.5 lm parameters, A6.5.1 lm parameter list, A6.5 – Yokogawa EJX930A User Manual
Page 138: A6-4
A6-4
IM 01C25R03-01E
A6.5 LM Parameters
A6.5.1 LM Parameter List
The tables below show LM parameters.
Meanings of Access column entries: RW = read/write possible; R = read only
Index
(SM)
Parameter Name
Sub-parameter Name
(Sub Index)
Default Factory
Setting
Access
Remarks
362 DLME_LINK_MASTER_CAPABILITIES_VARIABLE
0x04
RW
363 DLME_LINK_
MASTER_INFO_
RECORD
0
RW
1 MaxSchedulingOverhead
0
2 DefMinTokenDelegTime
100
3 DefTokenHoldTime
300
4 TargetTokenRotTime
4096
5 LinkMaintTokHoldTime
400
6 TimeDistributionPeriod
5000
7 MaximumInactivityToClaimLasDelay
2
8 LasDatabaseStatusSpduDistributionPeriod 6000
364 PRIMARY_LINK_MASTER_FLAG_VARIABLE
0
RW
LAS: True = 0xFF;
non-LAS: False = 0x00
365 LIVE_LIST_STATUS_ARRAY_VARIABLE
0
R
366 MAX_TOKEN_
HOLD_TIME_
ARRAY
0
RW
1 Element1
0
2 Element2
0
3 Element3
0
4 Element4
0
5 Element5
0
6 Element6
0
7 Element7
0
8 Element8
0
367 BOOT_OPERAT_FUNCTIONAL_CLASS
Specified at the time
of order
RW
0x01 (basic device);
0x02 (LM)
368 CURRENT_LINK_
SETTING_RECORD
0
R
Settings for LAS
1 SlotTime
0
2 PerDlpduPhlOverhead
0
3 MaxResponseDelay
0
4 FirstUnpolledNodeId
0
5 ThisLink
0
6 MinInterPduDelay
0
7 NumConseeUnpolledNodeId
0
8 PreambleExtension
0
9 PostTransGapExtension
0
10 MaxInterChanSignalSkew
0
11 TimeSyncClass
0
369 CONFIGURED_
LINK_SETTING_
RECORD
0
RW
1 SlotTime
4095
2 PerDlpduPhlOverhead
4
3 MaxResponseDelay
5
4 FirstUnpolledNodeId
37
5 ThisLink
0
6 MinInterPduDelay
12
7 NumConseeUnpolledNodeId
186
8 PreambleExtension
2
9 PostTransGapExtension
1
10 MaxInterChanSignalSkew
0
11 TimeSyncClass
4