6-7

IM 01C25R03-01E

6.3.8 Functions Relating to Flange

Temperature (option code: /DG1)

Flange temperature value reference:

In FLG_TEMP_VAL, it is possible to refer to

the flange temperature value and status. The

update period of this value is about 1 second.

The temperature unit is selected by XD_SCALE.

unit of the AI block, in which FLG_TEMP_VAL is

selected. The status is normally Good-Non Specific.

However, it turns to Bad or Uncertain when sensor

failure happens. For specifics, refer to Table

8.9. For details of Flange Temperature, refer to

APPENDIX 8.3.

6.3.9 BLOCK_ERR

BLOCK_ERR presents the cause of an error in the

block. The SENSOR transducer block checks the

following causes and sets the relevant bits.

BLOCK_ERR

Bit

Error

Cause

0 Other

Differential pressure adjusted

by zero/span adjustment out

of measurement range, Static

pressure adjusted by zero/span

adjustment out of measurement

range Pressure sensor failure,

Capsule temperature sensor

failure Electronic circuit failure

15 Out of Service MODE_BLK.Target is O/S

6.3.10 XD_ERROR

XD_ERROR is a parameter that contains codes

for the most significant errors that can occur in the

SENSOR transducer block. The errors of XD_

ERROR supported by EJX multivariable transmitter

and their causes are presented in the table below.

When multiple errors occur and their error codes

are different, the error with a larger code value is

stored first.

XD_ERROR

Bit

Error

Cause

15 Out of Service Sensor TB is in O/S mode.
18 Calibration

error

An error occurred during

calibration or a calibration error

has been detected.

20 Electronics

Failure

An electronic component has

failed.

22 I/O Failure

An I/O failure has occurred.

6.4 FLOW Transducer Block

6.4.1 Outline of the Functions

The differential pressure, static pressure and

external temperature signal calculated in the

SENSOR transducer block are input to this block,

and the flow calculation is performed based

on these signals. The result undergoes output

processing (e.g. damping), and the flow signal is

output to the AI function block.

6.4.2 Block Mode

The Block modes permitted for the FLOW

transducer block are Automatic (Auto) and Out

of Service (O/S). Note that the Automatic mode

cannot be set when option code A (Multi Sensing) is

selected in the measurement function.
For normal operation, select the Automatic mode.

To change important parameters, the O/S mode

must be selected. For details on how to identify

parameters that can be changed in the Automatic

mode and parameters that can be changed only in

the O/S mode, see chapter 9. Parameter Lists.

6.4.3 Calculation of the Flow

The calculated flow value and status are stored

to the FLOW_VALUE parameter. For details

on the flow calculation, refer to EJX910A and

EJX930A Multivariable Transmitters User's Manual

(IM 01C25R01-01E). The update period of the

flow calculation is 200 mseconds, and the flow

calculation is not updated when the operation mode

is O/S. Note that the Automatic mode cannot be

set when option code A (Multi Sensing) is selected

in the measurement function. There are two flow

calculation modes: Auto Compensation mode and

Basic mode. When flow calculation is performed

in the Auto Compensation mode, the calculation

coefficient must be calculated by the dedicated

setup tool and downloaded to the transmitter. For

details on this method, refer to the User's Manual

(IM 01C25R51-01E) for the dedicated setup tool.
The procedure for setting the BASIC Mode is as

follows. For details on how to calculate the Kfactor,

refer to the EJX910A and EJX930A Multivariable

Transmitters User's Manual (IM 01C25R01-01E).