4 function block parameters, Function block parameters -12 – Yokogawa EJX930A User Manual
Page 39
<5. Configuration>
5-12
IM 01C25R03-01E
Table 5.15
View Object for AI Function Block
Relative
Index Parameter Mnemonic
VIEW
1
2
3
4
1
ST_REV
2
2
2
2
2
TAG_DESC
3
STRATEGY
2
4
ALERT_KEY
1
5
MODE_BLK
4
4
6
BLOCK_ERR
2
2
7
PV
5
5
8
OUT
5
5
9
SIMULATE
10
XD_SCALE
11
11
OUT_SCALE
11
12
GRANT_DENY
2
13
IO_OPTS
2
14
STATUS_OPTS
2
15
CHANNEL
2
16
L_TYPE
1
17
LOW_CUT
4
18
PV_FTIME
4
19
FIELD_VAL
5
5
20
UPDATE_EVT
21
BLOCK_ALM
22
ALARM_SUM
8
8
23
ACK_OPTION
2
24
ALARM_HYS
4
25
HI_HI_PRI
1
26
HI_HI_LIM
4
27
HI_PRI
1
28
HI_LIM
4
29
LO_PRI
1
30
LO_LIM
4
31
LO_LO_PRI
1
32
LO_LO_LIM
4
33
HI_HI_ALM
34
HI_ALM
35
LO_ALM
36
LO_LO_ALM
37
OUT_D_SEL
2
38
OUT_D
2
Totals (# bytes)
31
26
33
48
Table 5.16
Indexes of View for Each Block
VIEW
1
2
3
4
Resourse Block
40100 40101 40102 40103
SENSOR Transducer
Block
40200 40201
40202
to
40203
40204
to
40206
FLOW Transducer
Block
40230 40231 40232
40233
to
40234
LCD Transducer Block 40250 40251 40252 40253
AI1 Function Block
40400 40401 40402 40403
AI2 Function Block
40410 40411 40412 40413
AI3 Function Block
40420 40421 40422 40423
AI4 Function Block
40430 40431 40432 40433
AI5 Function Block
40440 40441 40442 40443
PID Function Block
40800 40801 40802 40803
SC Function Block
41450 41451 41452 41453
IT Function Block
41600 41601 41602 41603
IS Function Block
41700 41701 41702 41703
AR Function Block
41750 41751 41752 41753
5.6.4 Function Block Parameters
Function block parameters can be read from the
host or can be set. For a list of the parameters of
blocks held by the EJX multivariable transmitter,
refer to “9.
PARAMETERS LISTS”. For the function blocks
other than AI block, LM function, software download
function and advanced diagnostic, refer to Appendix
1 to 8.